TP-6200 10/12 23Section 1 Specifications and Features

1.2.8 Communication Ports

The main logic circuit board contains several
communication ports for Modbusrand KBUS
connections. See Figure 1-12. Refer to the List of
Related Materials in the Introduction for corresponding
communication installation information.
1. P19—unused isolated connection (ISO2), RS-485 port
2. P21—KBUS isolated connection (ISO1), RS-485 port
3. P18—KBUS or Modbusr, RS-232 port
(Monitor III connection)
4. P20—Modbus, RS-485 port (Monitor III connection)
5. P22—ECM connector
6. Main logic circuit board
ADV-6533-A
12 34 5
6
Figure 1-12 Main Logic Circuit Board Communication
Ports (TopView of Circuit Board)
1.3 Controller Logic Specifications
Thecontroller logic specifications section is an overview
of the various features and functions of the controller.
Certain features function only when optional
accessories are connected. See Section 2, Operation,
for details.
The default selection time delays and relay driver
outputs (RDOs) are factory set and adjustable with the
programming mode on (Menu 14). Some data entries
require using a PC in the Remote Programming mode.
See the monitor software operation manual for details.
Inhibit Time Delay. The inhibit time delay is the time
period following crank disconnect during which the
generator set stabilizes and the controller does not
detect a fault or status event. Select the desired inhibit
time delay from 0 to 60 seconds.
TIme Delay (Shutdown or Warning). The time delay
follows the inhibit time delay. The time delay is the time
periodbetween when the controller first detects a fault or
status event and the controller warning or shutdown
lamp illuminates. The delay prevents any nuisance
alarms. Select the desired time delay from 0 to
60 seconds.

1.3.1 Status Event and Fault

Specifications

The table starting on the next page contains all status
events and faults with ranges and time delays including
items that do not have adjustments.
Note: The engine ECM may limit the crank cycle evenif
the controller is set to a longer time period.