TP-6200 10/12196 Appendix
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Analog Aux. Input
A04 ]
9A04
OIL TEMP
Default Valueswith
Warning Enabled:
HI/LO warning are
engine dependent
30 sec.
inhibit,
0 sec. delay
warning
Not adjustable
Analog Aux. Input
A06 VSG (Volvo,
GM, Doosan only)
9, 12 A06
ANALOG
AUXILIARY IN
Volvo:
0.5V=1250
4.5V=8750
GM/Doosan
60 Hz:
0.5V=2375
4.5V=2625
50 Hz:
0.5V=2327
4.5V=2624
Analog Aux. Input
A07
9, 11 A07
ANALOG VOLT
ADJUST
±10% of system
voltage over the range
of 0.5--4.5VDC
Battery Charger Fault
(see D01) **
Battle Switch
(Fault Shutdown
Override Switch)
9 BATTLE
SWITCH
Fixed Not adjustable
Block Heater
Control[[
10 BLOCK HEATER
CONTROL
RDO only
Breaker Trip w10 BREAKER
TRIP
RDO-30 Not adjustable
Common Protective
Relay Output w
10 COMMON PR
OUTPUT
RDO-31 wNot adjustable
Critical Overvoltage
Shutdown
10 CRITICAL
OVERVOLTAGE
Fixed 275 volts
(L1--L2)
Not adjustable
Cyclic Cranking 8 1--6 crank cycles
10--30sec. crank on
1--60sec. pause
3
15 sec.
15 sec.
Defined Common
Faults
(each input value is
set separately)
10 DEFINED
COMMON
FAULT
RDO-18
(lead 32A)
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Detonation Shutdown
(see D13) ]
Detonation Warning
(see D12) ]
Digital Aux. Input
D01--D21
9, 10 USER-DEFINED
D01--D21
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Input
D01 Battery Charger
Fault **
9, 10 D01 BATTERY
CHARGER
FAULT
RDO-11
(lead 61)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D02 Low Fuel
Warning **
9, 10 D02
LOW FUEL
WARNING
RDO-08
(lead 63)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D03 Low Coolant
Temperature**
9, 10 D03 LOW
COOLANT
TEMP
RDO-05
(lead 35)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D04 Field
Overvoltage (M4,
M5, or M7 alternator
only)
9, 10 D04
FIELD
OVERVOLTAGE
Fixed 1 sec.
inhibit,
15 sec.
delay
Not adjustable
* All models, except Waukesha-powered models. ** NFPAapplications
[Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
]Waukesha-powered models ]] FAA only
wParalleling applications