Relay

 

 

Inhibit

 

 

Status Event

Refer

 

Driver

 

Default

Time

Time

User-Defined

to

 

Output

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Range Setting

Selection

(sec.)

(sec.)

Settings

Analog Aux. Input

9

A04

 

Default Values with

30 sec.

 

 

Not adjustable

A04 ]

 

OIL TEMP

 

Warning Enabled:

inhibit,

 

 

 

 

 

 

 

 

HI/LO warning are

0 sec. delay

 

 

 

 

 

 

 

 

engine dependent

warning

 

 

 

Analog Aux. Input

9, 12

A06

 

 

Volvo:

 

 

A06 VSG (Volvo,

 

ANALOG

 

 

0.5V=1250

 

 

 

GM, Doosan only)

 

AUXILIARY IN

 

 

4.5V=8750

 

 

 

 

 

 

 

 

 

GM/Doosan

 

 

 

 

 

 

 

 

 

60 Hz:

 

 

 

 

 

 

 

 

 

0.5V=2375

 

 

 

 

 

 

 

 

 

4.5V=2625

 

 

 

 

 

 

 

 

 

50 Hz:

 

 

 

 

 

 

 

 

 

0.5V=2327

 

 

 

 

 

 

 

 

 

4.5V=2624

 

 

 

Analog Aux. Input

9, 11

A07

 

±10% of system

 

 

 

 

A07

 

ANALOG VOLT

 

voltage over the range

 

 

 

 

 

 

 

ADJUST

 

of 0.5--4.5 VDC

 

 

 

 

Battery Charger Fault

 

 

 

 

 

 

 

(see D01) **

 

 

 

 

 

 

 

 

Battle Switch

9

BATTLE

 

Fixed

 

 

 

Not adjustable

(Fault Shutdown

 

SWITCH

 

 

 

 

 

 

Override Switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Block Heater

10

BLOCK HEATER

RDO only

 

 

 

 

 

Control [[

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Breaker Trip w

10

BREAKER

RDO-30

 

 

 

 

Not adjustable

 

 

 

TRIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common Protective

10

COMMON PR

RDO-31 w

 

 

 

 

Not adjustable

Relay Output w

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Critical Overvoltage

10

CRITICAL

 

Fixed

275 volts

 

 

Not adjustable

Shutdown

 

OVERVOLTAGE

 

 

(L1--L2)

 

 

 

 

 

 

 

 

 

 

 

 

Cyclic Cranking

8

 

 

1--6 crank cycles

3

 

 

 

 

 

 

 

 

10--30 sec. crank on

15 sec.

 

 

 

 

 

 

 

 

1--60 sec. pause

15 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

Defined Common

10

DEFINED

RDO-18

Default shutdowns

30 sec.

0--60

0--60

 

Faults

 

COMMON

(lead 32A)

include:

inhibit,

 

 

 

(each input value is

 

FAULT

 

Emergency stop

5 sec. delay

 

 

 

set separately)

 

 

 

High coolant temp

 

 

 

 

 

 

 

 

 

Low oil pressure

 

 

 

 

 

 

 

 

 

Overcrank

 

 

 

 

 

 

 

 

 

Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

 

Detonation Shutdown

 

 

 

 

 

 

 

(see D13) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detonation Warning

 

 

 

 

 

 

 

(see D12) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

USER-DEFINED

 

 

30 sec.

0--60

0--60

 

D01--D21

 

D01--D21

 

 

inhibit,

 

 

 

 

 

 

 

 

 

5 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D01 BATTERY

RDO-11

Fixed

0 sec.

 

 

Not adjustable

D01 Battery Charger

 

CHARGER

(lead 61)

 

inhibit,

 

 

 

Fault **

 

FAULT

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D02

RDO-08

Fixed

0 sec.

 

 

Not adjustable

D02 Low Fuel

 

LOW FUEL

(lead 63)

 

inhibit,

 

 

 

Warning **

 

WARNING

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D03 LOW

RDO-05

Fixed

0 sec.

 

 

Not adjustable

D03 Low Coolant

 

COOLANT

(lead 35)

 

inhibit,

 

 

 

Temperature **

 

TEMP

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D04

 

Fixed

1 sec.

 

 

Not adjustable

D04 Field

 

FIELD

 

 

inhibit,

 

 

 

Overvoltage (M4,

 

OVERVOLTAGE

 

 

15 sec.

 

 

 

M5, or M7 alternator

 

 

 

 

delay

 

 

 

only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

** NFPA applications

 

 

 

[

Non-paralleling applications

 

 

[[ DDC/MTU engine with MDEC/ADEC

 

]

Waukesha-powered models

 

 

]] FAA only

 

 

 

 

w

Paralleling applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

196 Appendix

TP-6200 10/12

Page 196
Image 196
Kohler 20-3250 kW manual OIL Temp, Analog