| Relay |
|
| Inhibit |
|
|
Status Event | Refer |
| Driver |
| Default | Time | Time | ||
to |
| Output |
| Delay | Delay | ||||
or Fault | Menu | Digital Display | (RDO) | Range Setting | Selection | (sec.) | (sec.) | Settings | |
Analog Aux. Input | 9 | A04 |
| Default Values with | 30 sec. |
|
| Not adjustable | |
A04 ] |
| OIL TEMP |
| Warning Enabled: | inhibit, |
|
|
| |
|
|
|
|
| HI/LO warning are | 0 sec. delay |
|
|
|
|
|
|
|
| engine dependent | warning |
|
|
|
Analog Aux. Input | 9, 12 | A06 |
|
| Volvo: |
|
| — | |
A06 VSG (Volvo, |
| ANALOG |
|
| 0.5V=1250 |
|
|
| |
GM, Doosan only) |
| AUXILIARY IN |
|
| 4.5V=8750 |
|
|
| |
|
|
|
|
|
| GM/Doosan |
|
|
|
|
|
|
|
|
| 60 Hz: |
|
|
|
|
|
|
|
|
| 0.5V=2375 |
|
|
|
|
|
|
|
|
| 4.5V=2625 |
|
|
|
|
|
|
|
|
| 50 Hz: |
|
|
|
|
|
|
|
|
| 0.5V=2327 |
|
|
|
|
|
|
|
|
| 4.5V=2624 |
|
|
|
Analog Aux. Input | 9, 11 | A07 |
| ±10% of system |
|
|
|
| |
A07 |
| ANALOG VOLT |
| voltage over the range |
|
|
|
| |
|
|
| ADJUST |
| of |
|
|
|
|
Battery Charger Fault |
|
|
|
|
|
|
| — | |
(see D01) ** |
|
|
|
|
|
|
|
| |
Battle Switch | 9 | BATTLE |
| Fixed |
|
|
| Not adjustable | |
(Fault Shutdown |
| SWITCH |
|
|
|
|
|
| |
Override Switch) |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Block Heater | 10 | BLOCK HEATER | RDO only |
|
|
|
|
| |
Control [[ |
| CONTROL |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
Breaker Trip w | 10 | BREAKER |
|
|
|
| Not adjustable | ||
|
|
| TRIP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Common Protective | 10 | COMMON PR |
|
|
|
| Not adjustable | ||
Relay Output w |
| OUTPUT |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
Critical Overvoltage | 10 | CRITICAL |
| Fixed | 275 volts |
|
| Not adjustable | |
Shutdown |
| OVERVOLTAGE |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
Cyclic Cranking | 8 |
|
| 3 |
|
|
| ||
|
|
|
|
| 15 sec. |
|
|
| |
|
|
|
|
| 15 sec. |
|
|
| |
|
|
|
|
|
|
|
|
|
|
Defined Common | 10 | DEFINED | Default shutdowns | 30 sec. |
| ||||
Faults |
| COMMON | (lead 32A) | include: | inhibit, |
|
|
| |
(each input value is |
| FAULT |
| Emergency stop | 5 sec. delay |
|
|
| |
set separately) |
|
|
| High coolant temp |
|
|
|
| |
|
|
|
|
| Low oil pressure |
|
|
|
|
|
|
|
|
| Overcrank |
|
|
|
|
|
|
|
|
| Overspeed |
|
|
|
|
|
|
|
|
|
|
|
|
| |
Detonation Shutdown |
|
|
|
|
|
|
| — | |
(see D13) ] |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
Detonation Warning |
|
|
|
|
|
|
| — | |
(see D12) ] |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
Digital Aux. Input | 9, 10 |
|
|
| 30 sec. |
| |||
|
|
| inhibit, |
|
|
| |||
|
|
|
|
|
| 5 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
| |
Digital Aux. Input | 9, 10 | D01 BATTERY | Fixed | 0 sec. |
|
| Not adjustable | ||
D01 Battery Charger |
| CHARGER | (lead 61) |
| inhibit, |
|
|
| |
Fault ** |
| FAULT |
|
| 0 sec. delay |
|
|
| |
|
|
|
|
|
|
|
|
| |
Digital Aux. Input | 9, 10 | D02 | Fixed | 0 sec. |
|
| Not adjustable | ||
D02 Low Fuel |
| LOW FUEL | (lead 63) |
| inhibit, |
|
|
| |
Warning ** |
| WARNING |
|
| 0 sec. delay |
|
|
| |
|
|
|
|
|
|
|
|
| |
Digital Aux. Input | 9, 10 | D03 LOW | Fixed | 0 sec. |
|
| Not adjustable | ||
D03 Low Coolant |
| COOLANT | (lead 35) |
| inhibit, |
|
|
| |
Temperature ** |
| TEMP |
|
| 0 sec. delay |
|
|
| |
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D04 |
| Fixed | 1 sec. |
|
| Not adjustable | |
D04 Field |
| FIELD |
|
| inhibit, |
|
|
| |
Overvoltage (M4, |
| OVERVOLTAGE |
|
| 15 sec. |
|
|
| |
M5, or M7 alternator |
|
|
|
| delay |
|
|
| |
only) |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
* | All models, except | ** NFPA applications |
|
|
| ||||
[ |
|
| [[ DDC/MTU engine with MDEC/ADEC |
| |||||
] |
|
| ]] FAA only |
|
|
|
| ||
w | Paralleling applications |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
196 Appendix |
|