Factory-Defined Settings

 

 

 

 

Relay

 

 

 

 

Inhibit

 

Status Event

Refer

 

Driver

Alarm

 

 

Default

Time

Time

to

 

Output

 

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Horn

Lamp

Range Setting

Selection

(sec.)

(sec.)

 

 

 

 

 

 

 

 

 

 

Overcurrent

10

OVER

 

On

Warning

 

110%

 

10

 

 

 

CURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over Current PR

10

SD OVER

 

On

Shutdown

 

 

 

 

Shutdown w

 

CURRENT PR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overfrequency

7, 10

OVER

RDO-28

On

Shutdown

102%--140%

110% Std.

 

10

Shutdown

 

FREQUENCY

 

 

 

 

103% FAA

 

 

 

 

 

 

 

 

 

 

 

 

Over Power

10

SD OVER

 

On

Shutdown

 

102%

 

 

Shutdown w

 

POWER

 

 

 

 

Stdby

 

 

 

 

 

 

 

 

 

 

112% Prime

 

 

 

 

 

 

 

 

 

 

 

 

Overspeed

7, 10

OVER SPEED

RDO-01

On

Shutdown

65--70 Hz (60 Hz)

70 (60 Hz)

 

0.25

Shutdown

 

 

(lead 39)

 

 

55--70 Hz (50 Hz)

70 (50 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

Overvoltage

7, 8,

OVER

RDO-20

On

Shutdown

105%--135%

115%

 

2--10

Shutdown

10

VOLTAGE

(lead 26)

 

 

of nominal

2-sec time

 

 

 

 

 

 

 

 

 

 

delay[

 

 

 

 

 

 

 

 

 

 

135%

 

 

 

 

 

 

 

 

 

 

10-sec time

 

 

 

 

 

 

 

 

 

 

delayw

 

 

 

 

 

 

 

 

 

 

 

 

Password

 

 

 

 

 

 

 

 

 

(see Access Code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pre Lube Relay ]

10

PRE LUBE

RDO-26 ]

 

 

 

 

 

4

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Reset

 

 

 

 

 

 

 

 

 

(see D16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

 

 

 

 

 

 

 

 

(see D15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse Power

10

SD REVERSE

 

On

Shutdown

 

 

 

 

Shutdown w

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Sensor Fault

10

SPEED

RDO-24

On

Warning

 

 

 

 

 

 

 

SENSOR

 

 

 

 

 

 

 

 

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting Aid (see

 

 

 

 

 

 

 

 

 

Time Delay Starting

 

 

 

 

 

 

 

 

 

Aid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Ready

10

 

RDO-17

Off

System

 

 

 

 

 

 

 

 

(lead 60)

 

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Engine

8, 10

DELAY ENG

RDO-16

Off

 

00:00--10:00

5:00

 

 

Cooldown (TDEC)

 

COOLDOWN

(lead 70C)

 

 

min:sec

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Engine

8, 10

DELAY ENG

 

Off

 

00:00--5:00

00:01

 

 

Start (TDES)

 

START

 

 

 

min:sec

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Starting

8, 10

 

 

Off

 

0--10 sec.

 

 

 

Aid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Underfrequency

7, 10

UNDER

RDO-29 ]

On

Shutdown

80%--97%

97% FAA

 

10

 

 

 

FREQUENCY

 

 

 

 

90%[

 

 

 

 

 

 

 

 

 

 

80%w

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage

7, 8,

UNDER

RDO-27

On

Shutdown

70%--95%

85%

 

5--30

Shutdown

10

VOLTAGE

 

 

 

 

10-sec time

 

 

 

 

 

 

 

 

 

 

delay[

 

 

 

 

 

 

 

 

 

 

70%

 

 

 

 

 

 

 

 

 

 

30-sec time

 

 

 

 

 

 

 

 

 

 

delayw

 

 

 

 

 

 

 

 

 

 

 

 

Variable Speed

 

 

 

 

 

 

 

 

 

Governor (VSG)

 

 

 

 

 

 

 

 

 

(see A06)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VAR/PF Mode

 

 

 

 

 

 

 

 

 

(see D17)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Lower

 

 

 

 

 

 

 

 

 

(see D18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

 

** NFPA applications

 

 

 

[

Non-paralleling applications

 

 

 

[[ DDC/MTU engine with MDEC/ADEC

 

 

]

Waukesha-powered models

 

 

 

]] FAA only

 

 

 

w

Paralleling applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TP-6200 10/12

Section 1 Specifications and Features 29

Page 29
Image 29
Kohler 20-3250 kW SD Over, Current PR, Power, Over Speed, PRE Lube, SD Reverse, Sensor Fault, Delay ENG, Cooldown