Kohler 20-3250 kW manual Menu 10-Output Setup, Common Faults, Relay Driver Outputs RDOs

Models: 20-3250 kW

1 216
Download 216 pages 26.02 Kb
Page 64
Image 64

2.7.10 Menu 10—Output Setup

Menu 10 displays the setup of user-defined system, digital and analog status, and fault outputs and relay driver outputs (RDO) 1--31. These RDO outputs provide multiple choices for configuring customized auxiliary outputs. Additional individual outputs are available for monitoring, diagnostics, and control functions.

The user must enable the programming mode to edit the display. See Section 2.8.10 to change this menu.

Note: Some data require entry using a PC in the Remote Programming mode. See the Monitor Software operation manual for details.

Note: See Figure 2-8 in User Inputs for factory reserved inputs which are not user selectable.

Common Faults

The user can program a single fault comprised of faults from 3 common fault programs—system, digital, and analog faults.

Up to 62 user-defined system status events and faults are available. See Group B on the following pages for specific descriptions. The NFPA 110 faults are part of the system fault program and are comprised of 15 individual faults shown on the next page.

The user can select up to 21 user-defined digital status events and faults designated as D01 to D21. Each of the 21 status events and faults are assignable as shutdowns or warnings.

The user can select up to 7 user-defined analog status events and faults designated as A01 to A07. Each of the

7status events and faults are assignable as shutdowns or warnings with high or low settings for a total of up to

7status events and fault functions.

Relay Driver Outputs (RDOs)

Up to 31 RDOs are available using the system, digital, and analog status events and faults. RDOs provide only the driver. The contact relays that interface with other equipment are optional.

Note: Func(tion) Used By (RDO) XX Reassign? error message appears when the user attempts to duplicate an existing RDO selection.

Note: Cannot Change NFPA is Enabled. error message appears when the user attempts to modify RDO setting defaulted as NFPA 110 requirement.

Menu 10 Overview

MENU 10

OUTPUT SETUP

DEFINE COMMON

FAULTS

 

 

 

 

SYSTEM EVENTS

 

 

 

DIGITAL INPUTS

 

 

ANALOG INPUTS

 

 

RELAY DRV OUT XX

(see Group E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMMON FAULT

Y/N

 

COMMON FAULT

Y/N

 

COMMON FAULT

Y/N

 

COMMON FAULT Y/N

 

(see Group B)

 

 

(see Group C)

 

 

(see Group D)LO WARNING→

 

HI WARNING

 

 

 

 

 

 

 

 

 

 

 

Press down arrow to scroll

 

Press down arrow to scroll

 

Press down arrow to scroll

 

COMMON FAULT Y/N

 

through available faults.

 

 

through digital auxiliary

 

 

through analog auxiliary

 

 

 

 

 

 

 

 

 

LO SHUTDOWN

 

 

 

 

 

inputs.

 

 

inputs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMMON FAULT Y/N

 

 

 

 

 

 

 

 

 

 

 

 

HI SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM EVENTS

 

DIGITAL INPUTS

 

ANALOG INPUTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press down arrow to scroll through RDO’s 1--31 or enter RDO number.

 

 

 

 

 

 

 

 

 

 

RELAY DRV OUT XX Y/N

 

RELAY DRV OUT XX Y/N

 

RELAY DRV OUT XX Y/N

 

(see Group B)

 

(see Group C)

 

(see Group D)LO WARNING→

 

 

 

 

 

 

 

 

Press down arrow to scroll

 

Press down arrow to scroll

 

Press down arrow to scroll

 

through available RDO

 

through RDO digital auxiliary

 

through RDO analog

 

faults.

 

inputs.

 

auxiliary inputs.

RELAY DRV OUT Y/N HI WARNING

RELAY DRV OUT Y/N LO SHUTDOWN

RELAY DRV OUT Y/N HI SHUTDOWN

64 Section 2 Operation

TP-6200 10/12

Page 64
Image 64
Kohler 20-3250 kW manual Menu 10-Output Setup, Common Faults, Relay Driver Outputs RDOs, Menu 10 Overview