Over Current VR Shutdown. The lamp illuminates and the unit shuts down when the controller detects an overcurrent fault with voltage restraint. The local display shows sd over current pr. (Paralleling applications only.)

Overfrequency. The lamp illuminates and the unit shuts down when the frequency is above the overfrequency setting. The local display shows overfrequency. See Figure 2-3.

Overfrequency

 

Overfrequency

Setting Range

Time Delay

Default Setting

 

 

 

102%--140% of nominal

10 sec.

110% of nominal

 

 

 

Figure 2-3 Overfrequency Specs

Overpower. The lamp illuminates and the unit shuts down when the controller detects a fault in the paralleling system. The shutdown is set at 102% for standby and 112% for prime power applications. The local display shows over power. (Paralleling applications only.)

Overspeed. The lamp illuminates and the unit shuts down immediately when the governed frequency on 50 and 60 Hz models exceeds the overspeed setting for

0.25seconds. The local display shows overspeed. See Figure 2-4 for overspeed specs.

Generator

 

Overspeed

Overspeed Default

Set

Time Delay

Range Hz

Setting Hz

Frequency Hz

 

 

 

 

 

 

 

60

0.25 sec.

65--70

70

 

 

 

 

50

0.25 sec.

55--70

70

 

 

 

 

Figure 2-4 Overspeed Specs

Overvoltage. The lamp illuminates and the unit shuts down when the voltage exceeds the overvoltage setting for the time delay period. The local display shows overvoltage. Overvoltage specifications follow. See Figure 2-5.

Note: Overvoltage can damage sensitive equipment in less than one second. Install separate overvoltage protection on online equipment requiring faster than 2-second shutdown.

 

 

Overvoltage

 

Overvoltage

Time

Default Setting

Overvoltage

Setting

Delay

without

Default Setting

Range

Range

Paralleling

with Paralleling

 

 

 

 

105%--135%

2--10 sec.

115% at 2 sec.

135% at 10 sec.

of nominal

 

 

 

 

 

 

 

Figure 2-5 Overvoltage Specs

Reverse Power. The lamp illuminates and the unit shuts down when the controller detects a reverse power condition. The reverse power relay senses AC power flow into the generator set. If the generator set is being feed power or being ”motored” by another generator set or the utility, the reverse power relay senses this AC power flow and opens the generator set circuit breaker. The local display shows sd reverse power. (Paralleling applications only.)

Underfrequency. The lamp illuminates and the unit shuts down when the frequency falls below the underfrequency setting. The local display shows underfrequency. See Figure 2-6.

 

 

Underfrequency

 

Underfreq.

 

Default Setting

Underfrequency

Setting

Time

without

Default Setting

Ranger

Delay

Paralleling

with Paralleling

 

 

 

 

80%--95%

10 sec.

90% of nominal

80% of nominal

of nominal

 

 

 

Figure 2-6 Underfrequency Specs

 

Undervoltage. The lamp illuminates and the unit shuts down when the voltage falls below the undervoltage setting for the time delay period. The local display shows undervoltage. Undervoltage specifications follow. See Figure 2-7.

 

 

Undervoltage

 

Undervoltage

 

Default Setting

Undervoltage

Setting

Time Delay

w-o/Parallelin

Default Setting

Range

Range

g

w/Paralleling

 

 

 

 

70%--95% of

5--30 sec.

85% of nominal

70% of nominal

nominal

at 10 sec.

at 30 sec.

 

 

 

 

 

Figure 2-7 Undervoltage Specs

40 Section 2 Operation

TP-6200 10/12

Page 40
Image 40
Kohler 20-3250 kW manual Overfrequency Specs