Over Current VR Shutdown. The lamp illuminates and the unit shuts down when the controller detects an overcurrent fault with voltage restraint. The local display shows sd over current pr. (Paralleling applications only.)
Overfrequency. The lamp illuminates and the unit shuts down when the frequency is above the overfrequency setting. The local display shows overfrequency. See Figure
Overfrequency |
| Overfrequency |
Setting Range | Time Delay | Default Setting |
|
|
|
10 sec. | 110% of nominal | |
|
|
|
Figure 2-3 Overfrequency Specs
Overpower. The lamp illuminates and the unit shuts down when the controller detects a fault in the paralleling system. The shutdown is set at 102% for standby and 112% for prime power applications. The local display shows over power. (Paralleling applications only.)
Overspeed. The lamp illuminates and the unit shuts down immediately when the governed frequency on 50 and 60 Hz models exceeds the overspeed setting for
0.25seconds. The local display shows overspeed. See Figure
Generator |
| Overspeed | Overspeed Default |
Set | Time Delay | Range Hz | Setting Hz |
Frequency Hz |
|
|
|
|
|
|
|
60 | 0.25 sec. | 70 | |
|
|
|
|
50 | 0.25 sec. | 70 | |
|
|
|
|
Figure 2-4 Overspeed Specs
Overvoltage. The lamp illuminates and the unit shuts down when the voltage exceeds the overvoltage setting for the time delay period. The local display shows overvoltage. Overvoltage specifications follow. See Figure 2-5.
Note: Overvoltage can damage sensitive equipment in less than one second. Install separate overvoltage protection on online equipment requiring faster than
|
| Overvoltage |
|
Overvoltage | Time | Default Setting | Overvoltage |
Setting | Delay | without | Default Setting |
Range | Range | Paralleling | with Paralleling |
|
|
|
|
115% at 2 sec. | 135% at 10 sec. | ||
of nominal |
|
|
|
|
|
|
|
Figure 2-5 Overvoltage Specs
Reverse Power. The lamp illuminates and the unit shuts down when the controller detects a reverse power condition. The reverse power relay senses AC power flow into the generator set. If the generator set is being feed power or being ”motored” by another generator set or the utility, the reverse power relay senses this AC power flow and opens the generator set circuit breaker. The local display shows sd reverse power. (Paralleling applications only.)
Underfrequency. The lamp illuminates and the unit shuts down when the frequency falls below the underfrequency setting. The local display shows underfrequency. See Figure 2-6.
|
| Underfrequency |
| |
Underfreq. |
| Default Setting | Underfrequency | |
Setting | Time | without | Default Setting | |
Ranger | Delay | Paralleling | with Paralleling | |
|
|
|
| |
10 sec. | 90% of nominal | 80% of nominal | ||
of nominal | ||||
|
|
| ||
Figure |
|
Undervoltage. The lamp illuminates and the unit shuts down when the voltage falls below the undervoltage setting for the time delay period. The local display shows undervoltage. Undervoltage specifications follow. See Figure 2-7.
|
| Undervoltage |
| |
Undervoltage |
| Default Setting | Undervoltage | |
Setting | Time Delay | Default Setting | ||
Range | Range | g | w/Paralleling | |
|
|
|
| |
85% of nominal | 70% of nominal | |||
nominal | at 10 sec. | at 30 sec. | ||
| ||||
|
|
|
|
Figure 2-7 Undervoltage Specs