2.8.10 Menu 10—Output Setup

Menu 10 provides setup of the user-defined system, digital and analog status and fault outputs, and relay driver outputs (RDO) 1--31. These outputs provide a multitude of choices for configuring customized auxiliary outputs. Additional individual outputs are available for monitoring, diagnostic, and control functions.

The user must enable the programming mode to edit the display.

Note: Some data require entry using a PC in the Remote Programming mode. See the monitor software operation manual for details.

Common Faults

The user can program a single fault comprised of status and fault events from 3 common fault programs— system, digital, and analog faults.

Up to 66 user-defined system events are available, which provide status and fault information. See Group B on the following pages for specific descriptions. The NFPA-110 faults are part of the system fault program and are comprised of 15 individual faults shown on this page.

Up to 21 user-defined digital status and fault events designated as D01 to D21 are available. Each of the 21 status events and faults are assignable as shutdowns or warnings.

Up to 7 user-defined analog status events and faults designated as A01 to A07 are available. Each of the

7status events and faults are assignable as shutdowns or warnings with high or low settings for a total of up to

7status events and fault functions.

Relay Driver Outputs (RDOs)

Up to 31 RDOs are available using the system, digital, and analog status events and faults. RDOs provide only the relay driver, not the relay. The contact relays that interface with other equipment are user supplied.

Note: Func(Function) Used by (RDO) XX Reassign? appears when the user attempts to assign an RDO to a function already assigned.

Note: Cannot Change (because the) NFPA is Enabled appears when the user attempts to modify an RDO setting that is a NFPA 110 default requirement.

Software Controlled RDOs (SCRDOs)

The SCRDO is set up and enabled using the keypad or PC. See the monitor software operation manual when reactivating the SCRDO. The user can deactivate an SCRDO at the controller. The user cannot reactivate the SCRDO at the controller. The procedure to deactivate the SCRDO appears at the end of Menu 10—Output Setup, Displays with Entry Keys—Deactivating the SCRDO. The user must enable the programming mode to edit the display.

NFPA 110 Faults

The 15 NFPA 110 fault alarms include the following:

DOverspeed

DOvercrank

DHigh Coolant Temperature Shutdown

DOil Pressure Shutdown

DLow Coolant Temperature

DHigh Coolant Temperature Warning

DOil Pressure Warning

DLow Fuel

DMaster Not in Auto

DBattery Charger Fault

DLow Battery Voltage

DHigh Battery Voltage

DLow Coolant Level

DEPS Supplying Load

DAir Damper Indicator

Defined Common Faults

The 5 defined common faults include the following:

DEmergency Stop

DHigh Coolant Temperature Shutdown

DOil Pressure Shutdown

DOvercrank

DOverspeed

104 Section 2 Operation

Local Programming Mode On

TP-6200 10/12

Page 104
Image 104
Kohler 20-3250 kW manual Software Controlled RDOs SCRDOs Nfpa 110 Faults, Defined Common Faults