If the engine speed is low, adjust it to the rated r.p.m. * Refer to Step
Refer to Section 7 “RANGE OF APPLICATIONS” for the wattage of the appliances. If the generator is
If the appliance is faulty, repair it.
HEATED.
If the cooling air inlet and/or cooling air outlet is clogged with dirt, grass, chaff or other debris, remove it.
AIR OUTLET
Fig. 1
Stop the engine. Measure the insulation resistance between the live terminal of the receptacle and the ground terminal.
If the insulation resistance is less than 1 MQ, dis- assemble the generator and check the insulation resistance of the stator, rotor and the live parts in the control box. (Refer to Section
Any part where the insulation resistance is less than 1 MQ, the insulation is faulty and may cause electric leakage.
Replace the faulty part.
Fig.