Voltage drop indicates as V =

NOTES: Wiring between generator and electrical appliances

7.Allowable current of cable

Use a cable with an allowable current that is higher than the rated input current of the load (electrical appliance). If the input current is higher than the allowable current of the cable used, the cable will become excessively heated and deteriorate the insulation, possibly burning it out.

Table 7-2 shows cables and their allowable currents for your reference.

2.Cable length

If a long cable is used, a voltage drop occurs due to the increased resistance in the conductors decreasing the input voltage to the load (electrical product). As a result, the load can be damaged. Table 7-2 shows voltage drops per 100 meters of cable.

 

 

 

 

 

 

 

 

 

 

Current Amp.

mm’

No.

A

 

No. I mm

 

QllOOm

1A

3A

XJyJ-yA

 

0.75

18

7

 

30 IO.18

 

2.477

2.5U

8U

 

 

1.27

16

12

 

5010.18

 

1.486

1.5u

5u

 

 

2.0

14

17

 

37 IO.26

 

0.952

1u

3u

 

 

3.5

112-101

23

1

45

IO.32

I

0.517

I -

I 1.5u

 

 

5.5

10-8

25

 

70

I 0.32

 

0.332

-

1U

2u

2.5U I3.5U 4U 5U

 

 

 

 

 

 

Table

7-2

 

 

 

 

Voltage drop indicates as V =

Rmens resistance ( Q /lo0 m) on the above table. I means electric current through the wire (A).

f2 means the length of the wire (m).

The length of wire indicates round length,it means twice the length from generator to electrical tools.

- 42 -