Specific Applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Waukesha-

with Menu 15

DDC/MTU

Other

Input

 

Non-ECM

 

Powered

(Paralleling

Engine with

Specialized

Type

ECM Engine

Engine

NFPA 110

Engine

Application)

MDEC/ADEC

Application

 

 

 

 

 

 

 

 

Analog Inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

X

Coolant

X

Coolant

X

X

X

Temperature *

Temperature *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A2

X

Oil Pressure *

X

Oil Pressure *

X

X

X

 

 

 

 

 

 

 

 

A3

X

X

X

Intake Air

X

X

X

Temperature *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oil

 

 

 

A4

Fuel Level *

Fuel Level *

Fuel Level *

Temperature

Fuel Level *

Fuel Level *

Fuel Level *

 

 

 

 

Warning *

 

 

 

 

 

 

 

 

 

 

 

A5

X

X

X

X

X

X

X

 

 

 

 

 

 

 

 

A6

X

X

X

X

X

X

X (8) *

 

 

 

 

 

 

 

 

A7 (9)

Voltage Adjust

Voltage Adjust

Voltage Adjust

Voltage Adjust

Voltage Adjust

Voltage Adjust

Voltage Adjust

 

 

 

 

 

 

 

 

Digital Inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1

X

X

Battery Charger Fault *

X

X

X

X

 

 

 

 

 

 

 

 

D2

X

X

Low Fuel Warning *

X

X

X

X

 

 

 

 

 

 

 

 

D3

Low Coolant

X

Low Coolant Temp.*

X

X

X

X

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D4

X

X

X

X

X

X

X (1) *

 

 

 

 

 

 

 

 

D5

X

X

X

X

Breaker

X

X

Closed *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6

X

X

X

X

Enable Synch *

X

X

 

 

 

 

 

 

 

 

D7

X

X

X

X

X

X

X

 

 

 

 

 

 

 

 

D8

X

X

X

X

X

X

X

 

 

 

 

 

 

 

 

D9

X

X

X

X

X

X

X (2) *

 

 

 

 

 

 

 

 

D10

X

X

X

X

X

X

X

 

 

 

 

 

 

 

 

D11

X

X

X

AFM

X

X

X

Shutdown *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D12

X

X

X

Deton

X

X

X

Warning *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D13

X

X

X

Deton/Knock

X

X

X

Shutdown *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D14

X

X

Low Coolant Level

X

X

X

X

(with LCL Switch) *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D15

X

X

X

X

X

X

X (3) *

 

 

 

 

 

 

 

 

D16

X

X

X

X

X

X

X (4) *

 

 

 

 

 

 

 

 

D17

X

X

X

X

X

X

X (5) *

 

 

 

 

 

 

 

 

D18

X

X

X

X

X

X

X (6) *

 

 

 

 

 

 

 

 

D19

X

X

X

X

X

X

X (7) *

 

 

 

 

 

 

 

 

D20

X

X

Air Damper *

X

X

X

X

 

 

 

 

 

 

 

 

D21

Idle Mode

X

X

X

X

X

X

Active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) D4 is preassigned as Field Overvolts when using a Marathon M4/M5/M7/M10 alternator.

(2) D9 is preassigned as Low Fuel Shutdown when using 125RZG (GM powered).

(3) D15 is preassigned as Remote Shutdown.

(4) D16 is preassigned as Remote Reset.

(5) D17 is preassigned as VAR/PF mode.

(6) D18 is preassigned as Voltage Lower.

(7) D19 is preassigned as Voltage Raise.

(8) A6 is preassigned as Variable Speed Governor (VSG) (Volvo, GM, and Doosan engines only)

(9) A7 is default location, however the default function is not Analog Voltage Adjust; the function must be enabled. See Section 1.3.3. * Factory-reserved inputs that are fixed and not user-changeable.

Figure 2-8 User Inputs (X) and Factory-Reserved Inputs (as shown)

42 Section 2 Operation

TP-6200 10/12

Page 42
Image 42
Kohler 20-3250 kW manual Ddc/Mtu, Mdec/Adec