Menu 15—Protective Relays, continued

Menu 15 Displays with Key Entries

Key

 

 

Entry

Display

Description

 

PR UNDERFREQUENCY

 

?%

#HZ

 

 

 

 

 

 

 

PR UNDERFREQUENCY

 

#%

#HZ

 

 

 

 

 

 

 

TIME DELAY

 

?SEC

 

 

 

 

 

TIME DELAY

 

#SEC

 

 

 

 

 

 

 

 

PR UNDERFREQUENCY

 

?%

#HZ

 

 

 

 

PR REVERSE POWER

 

?%

#KW

 

 

 

 

 

 

 

PR REVERSE POWER

 

#%

#KW

 

 

 

 

TIME DELAY

 

?SEC

 

 

 

 

 

TIME DELAY

 

#SEC

 

 

 

 

 

PR REVERSE POWER

 

?%

#KW

 

 

 

 

SD REVERSE POWER

 

?%

#KW

 

 

 

 

 

 

 

SD REVERSE POWER

 

#%

#KW

 

 

 

 

TIME DELAY

 

?SEC

 

 

 

 

 

TIME DELAY

 

#SEC

 

 

 

 

 

SD REVERSE POWER

 

?%

#KW

 

 

 

 

 

 

 

PR OVER POWER

 

?%

#KW

 

 

 

 

PR OVER POWER

 

#%

#KW

 

 

 

 

TIME DELAY

 

?SEC

 

 

 

 

 

TIME DELAY

 

#SEC

 

 

 

 

 

PR OVER POWER

 

?%

#KW

Displays the underfrequency % value. When required, use the numeric keys to enter the desired underfrequency % value and press the Enter key.

Displays the corrected underfrequency % value.

Displays the underfrequency time delay. When required, use the numeric keys to enter the desired time delay value and press the Enter key.

Displays the corrected underfrequency time delay value.

Returns the user to the underfrequency % value display.

Displays the reverse power % value. When required, use the numeric keys to enter the desired reverse power % value and press the Enter key.

Displays the corrected reverse power % value.

Displays the reverse power time delay. When required, use the numeric keys to enter the desired time delay value and press the Enter key.

Displays the corrected reverse power time delay value.

Returns the user to the reverse power % value display.

Displays the reverse power shutdown % value. When required, use the numeric keys to enter the desired reverse power shutdown % value and press the Enter key.

Displays the corrected reverse power shutdown % value.

Displays the reverse power shutdown time delay. When required, use the numeric keys to enter the desired time delay value and press the Enter key.

Displays the corrected reverse power shutdown time delay value.

Returns the user to the reverse power shutdown % value display.

Displays the over power % value. When required, use the numeric keys to enter the desired over power % value and press the Enter key.

Displays the corrected over power % value.

Displays the over power time delay. When required, use the numeric keys to enter the desired time delay value and press the Enter key.

Displays the corrected over power time delay value.

Returns the user to the over power % value display.

132 Section 2 Operation

Local Programming Mode On

TP-6200 10/12

Page 132
Image 132
Kohler 20-3250 kW manual Menu 15-Protective Relays