Menu 10 Overview, continued

Group B

For defined system events, choose from the following 66 status events and faults by changing selection to YES. See Appendix E for application and restrictions with specific engines.

EMERGENCY STOP

OVER SPEED

OVER CRANK

HI COOL TEMP SHUTDWN

OIL PRESS SHUTDOWN

LOW COOLANT TEMP (non-ECM engines)

LOW FUEL

HI COOL TEMP WARNING

OIL PRES WARNING

MASTER NOT IN AUTO

NFPA 110 FAULT*

LOW BATTERY VOLTAGE

HIGH BATTERY VOLTAGE

BATTERY CHARGE FAULT

SYSTEM READY

LOSS OF ECM COMM (ECM engines)

NO OIL PRESS SIGNAL

HI OIL TEMP

NO COOL TEMP SIGNAL

LOW COOLANT LEVEL

SPEED SENSOR FAULT

LOCKED ROTOR

MASTER SWITCH ERROR

MASTER SWITCH OPEN

MASTER SWITCH TO OFF

AC SENSING LOSS

OVER VOLTAGE

UNDER VOLTAGE

WEAK BATTERY

OVER FREQUENCY

UNDER FREQUENCY

LOAD SHED KW OVER

LOAD SHED UNDER FREQ

OVER CURRENT

EPS SUPPLYING LOAD

INTERNAL FAULT

DELAY ENG COOLDOWN

DELAY ENG START

STARTING AID

GENERATOR RUNNING

AIR DAMPER CONTROL

GROUND FAULT

EEPROM WRITE FAILURE

CRITICAL OVERVOLTAGE

ALTERNATOR PROTECTION

SHUTDOWN

AIR DAMPER INDICATOR

DEFINED COMMON FAULT (RDO only)[ SCRDOs 1--4 (software controlled RDOs)

MAINTENANCE DUE

ENGINE DERATE ACTIVE

ENGINE STALLED

J1939 CAN SHUTDOWN

*NFPA 110 FAULT

The 15 NFPA 110 Fault Alarms include the following:

OVERSPEED

OVERCRANK

HIGH COOLANT TEMP SHUTDOWN OIL PRESSURE SHUTDOWN LOW COOLANT TEMPERATURE HIGH COOLANT TEMP WARNING OIL PRESSURE WARNING

LOW FUEL

MASTER NOT IN AUTO BATTERY CHARGER FAULT LOW BATTERY VOLTAGE HIGH BATTERY VOLTAGE LOW COOLANT LEVEL EPS SUPPLYING LOAD AIR DAMPER INDICATOR

[DEFINED COMMON FAULT

The 5 defined common faults include the following:

EMERGENCY STOP

HI COOL TEMP SHUTDOWN OIL PRESS SHUTDOWN OVERCRANK OVERSPEED

Group B, continued

Paralleling applicatons:

SD REVERSE POWER

SD OVER POWER

SD LOSS OF FIELD

SD OVERCURRENT PR

COMMON PR OUTPUT

IN SYNCH

BREAKER TRIP

Waukesha-powered models:

FUEL VALVE RELAY

PRELUBE RELAY

AFM REMOTE START

NO OIL TEMP SIGNAL

HI OIL TEMP WARNING

NO AIR TEMP SIGNAL

INTAKE AIR TEMP WARN

INTAKE AIR TEMP SDWN

AFM ENG START DELAY

DDC/MTU engine with MDEC/ADEC:

HI OIL TEMP WARNING

INTAKE AIR/TEMP WARN

INTAKE AIR TEMP SDWN

ECM YELLOW ALARM

ECM RED ALARM

BLOCK HEATER CONTROL

LOW COOL TEMP SDOWN

LOAD SHED OVER TEMP

Group C

Up to 21 user-defined digital status events and fault inputs designated as D01 to D21 can result in a digital input common fault.

Group D

Up to 7 analog inputs, user- defined status events and faults designated as A01 to A07. Each of the 7 is assignable as a shutdown or warning with high or low settings.

Group E

Choose up to 31 status event and fault RDOs from the following:

SYSTEM FAULTS

(see Group B, 66 Items)

DIGITAL INPUTS

(see Group C, 21 Items)

ANALOG INPUTS (see Group D, 7 Items)

TP-6200 10/12

Section 2 Operation 65

Page 65
Image 65
Kohler 20-3250 kW manual Defined Common Fault