13.Place the generator set master switch to the RUN position to start the generator set. Refer to the respective generator set operation manual as needed.

14.Listen and observe the fan operation.

15.Immediately shut down the generator set if abnormal noise or fan assembly vibration is observed. Correct the problem and go back to step 13.

16.After several minutes of generator set operation without abnormal noise or vibration, shut down the generator set by placing the generator set master switch to the OFF/RESET position.

3.9Radiator Expansion Joint Loosening—Initial Setup Only

Loosen the radiator expansion joint nuts on 1200--2000 kW generator sets that have radiators manufactured by Young Radiator Company. Expansion joints located on each side of the radiator permit differential thermal expansion of the radiator tank. The factory tightens the 12 expansion joint nuts before generator set shipment. Loosen the expansion joint nuts one full turn before running the generator set. See Figure 3-13.

4

1

2

3

1. Air flow

TP-5353-3

 

2.Expansion joint nuts for rear tank, left side

3.Expansion joint nuts for front tank, left side

4.Top front of radiator

Figure 3-13 Expansion Joint Nuts, Top Left Side of Radiator, Typical

3.10Radiator Fan Bearing Lubrication

The following procedure applies only to 1200 kW and larger generator sets. Lubricate the radiator fan shaft and idler shaft bearings at every engine oil change to avoid bearing damage. Lubricate the bearings every 200 hours of operation when the generator set runs in ambient temperatures below 29°C (85°F) or when the generator set runs in a dusty and/or humid environment.

Lubrication and Drive Belt Adjustment Procedure

Lubricate the fan shaft and idler shaft bearings with a lithium-complex base, multi-purpose grease with antirust, antifoam, and extreme-pressure additives having a minimum dropping point of 204°C (400°F). Use Mobil Mobilith AW2 NLGI Grade 2 or equivalent.

1.Place the generator set master switch in the OFF/RESET position.

2.Disconnect the generator set engine starting battery(ies), negative (--) lead first, and disconnect power to the battery charger.

3.Remove the belt guards to expose the fan shaft and idler shaft bearings.

4.Inject grease into the two bearings on the fan shaft block and the two bearings on the idler shaft block using a grease gun until a 3--6 mm (0.13--0.25 in.) grease column shows at the bearing pressure relief port. See Figure 3-14.

Note: The fan shaft and idler shaft bearings have pressure relief ports to prevent bearing damage caused by overlubrication.

 

1

 

5

 

2

 

4

 

2

 

3

 

TP-5353-3

 

1

1.

Grease fittings

2.

Pressure relief port

3.

Radiator assembly

4.

Idler shaft grease fittings

5.

Fan shaft grease fittings

Figure 3-14 Radiator Fan Bearings and Pressure Relief Ports, Typical

148 Section 3 Scheduled Maintenance

TP-6200 10/12

Page 148
Image 148
Kohler 20-3250 kW manual Radiator Expansion Joint Loosening-Initial Setup Only, Radiator Fan Bearing Lubrication