TP-6200 10/1248 Section 2 Operation
2.5.2 Auto-Scroll Function
Theauto-scroll function continuously shows voltage and
currentdata from Menu 1—Generator Monitoring, V & A
Summary without the need to press the down arrow for
each display.
For auto-scroll function press ENTER at the V & A
Summary menu. Press the Reset Menu key or Menu
Right key to stop the auto-scroll function.
2.5.3 Request and Error Messages
Note: When EEPROM errors occur or initializing the
EEPROM is required, contact an authorized
distributor/dealer.

Request and Status Messages

Display messages require the user to enter additional
data, confirm the previous entry or require time to
process as described below.
Entry Accepted appears for several seconds after
pressing the Enter key during the programming mode.
The display then shows the new data.
Initialize EEPROM? Prompt to confirm EEPROM
initialization.
Reset Complete indicates the user has successfully:
DReset the maintenance records or
DRestoredthe AC analog inputs to the default settings.
DRestored voltage regulator settings to the defaults.
Right Arrow directs the user to the next menu. The
menus loop; press the right arrow key to move to the
next menu.
Setup Complete indicatesthe completion of the analog
input setup.
SetupLocked appears when user attempts to change a
value or perform a function available only when the
system is unlocked.
Setup Unlocked appears when user has unlocked the
system for maintenance or troubleshooting.
(Question) ? asked by the controlfirmware; answer the
questionby pressing the yes/no, numeric digit, or am/pm
key.
Wait for System Reset (6 Sec) appears while the
EEPROM initializes.

Error Messages

When an error message appears, the entered
informationis not within the allowable parameters set by
the control firmware or is not permitted as described
below. In cases where the data was outside the
parameters, press the Reset Menu key and enter the
corrected information.
Access Denied appears when the user attempts to:
DEnter data prohibited by the master switch position,
DEnter data prohibited by the generator set state, or
DEnable the LDD (load disturbance detection).
Access Denied Idle Mode Active appears when the
userattempts to modify the voltage regulator setup while
the idle mode is active.
AlarmActive appears when the user attempts to modify
an analog or a digital input that is active. See Menu
9—Input Setup.
Cannot Change (because the) NFPA is Enabled
appears when the user attempts to modify an RDO
setting that is a NFPA 110default requirement.
Cannot Change Preset appears when the user
attempts to change the factory preset analog input,
digital input, or input parameter.
EEPROM Write Error appears when a component
failure occurs. Contact an authorized distributor/dealer.
Entry Unacceptable appears when the user attempts
an invalid input to the voltage regulator setup.
Some alternators are intended to operate within a
specific, limited range of conditions (voltage, frequency,
and phase or connection). The following error messages
can appear when attempts are made to enter system
values that do not match acceptable conditions for the
particular alternator.
DFixed Frequency when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.
DFixed Phase when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.