Kohler 20-3250 kW manual Modbus Communications, Remote Single Connection, Remote Area Network

Models: 20-3250 kW

1 216
Download 216 pages 26.02 Kb
Page 51
Image 51

Remote Single Connection

A modem connects a PC to a single device. The PC communicates with the device via a telephone network. Locate the PC anywhere a telephone line is available. See Figure 2-14.

Remote Area Network

A PC connects to a modem. The devices connect to a LAN network. The PC communicates to the devices via a telephone network that is interfaced to the LAN

network. Acceptable devices include the Decision- Makerr 550 controller, Decision-Makerr 340 controller, M340 transfer switch control, M340+ transfer switch control, and PM340 power monitor. Locate the PC anywhere a telephone line is available. See Figure 2-15.

The 550 controller can be used as an RS-232 to RS-485 port converter in a LAN network if the 550 controller is located within 15 m (50 ft.) of the device modem. This configuration is the Remote LAN Conv option.

 

 

 

 

Generator Set

 

 

Modem

Modem

Controller or

 

 

Transfer Switch

 

 

 

 

 

 

 

 

Control

 

RS-232

 

 

RS-232

Personal

up to

Telephone

 

up to

Computer

15 m (50 ft.)

Lines

 

15 m (50 ft.)

Figure 2-14 Remote Single Connection

 

 

 

 

Generator Set

Generator Set

 

 

 

 

Controller or

Controller or

 

 

 

 

Transfer Switch

Transfer Switch

 

 

 

 

Control

Control

Modem

 

Modem

RS-232 to RS-485

 

 

 

port converter

 

 

 

 

 

 

 

 

 

 

RS-485

Generator Set

Generator Set

Personal

Telephone

 

up to 1220 m

Controller or

Controller or

Computer

Lines

 

(4000 ft.)

Transfer Switch

Transfer Switch

 

 

 

 

Control

Control

Figure 2-15 Remote Area Network

2.6.2Modbus Communications

The controller communicates using Modbusr as a slave connection with the Modbusr master initiating the communication. The controller seeks the system and alternator parameters and diagnostic information then responds back to the Modbusr master. In addition, the controller accepts information to alter controller parameters including generator set starting and stopping. See Figure 2-16. Refer to the List of Related Materials for available Modbusr literature.

RS-485

 

up to 1220 m (4000 ft.)

 

Generator Set

Modbusr Master

Controller

 

RS-232

 

up to 15 m (50 ft.)

 

Figure 2-16 Modbusr Connections

 

Note: Only one Modbusr master can be connected to the 550 controller. Examples include the remote serial annunciator, Monitor III, and switchgear applications.

Modbusr is a registered trademark of Schneider Electric.

TP-6200 10/12

Section 2 Operation 51

Page 51
Image 51