Menu 12—Calibration, continued

Menu 12 Displays with Key Entries (Scale AC Analog Inputs)

Key

 

 

Entry

Display

Description

GEN L2-L0 V

#

CALIB REF

?.?

AND

 

 

GEN L2-L0 V

#

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L2-L0 V

#

 

 

 

CALIB REF

#.#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L3-L0 V

#

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

 

 

 

 

GEN L3-L0 V

#

 

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L3-L0 V

#

 

 

 

 

CALIB REF

#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN VOLTAGE LN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN VOLTAGE LL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L1-L2 V

#

 

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L1-L2 V

#

 

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L1-L2 V

#

 

 

 

 

CALIB REF

#.#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L2-L3 V

#

 

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

 

 

 

Measure the generator set output voltage for three-phase models between L2-L0 using a voltmeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

Three-Phase Models only. Measure the generator set output voltage for three-phase models between L3-L0 using a voltmeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

Returns the user to the generator set voltage line-to-neutral heading.

Displays the generator set voltage line-to-line heading.

Note: The generator set must be running for the following steps.

Measure the generator set output voltage for single and three-phase models between L1-L2 using a voltmeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

Three-Phase Models only. Measure the generator set output voltage for three-phase models between L2-L3 using a voltmeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Note: The generator set must be running for the following steps.

GEN L2-L3 V

#

CALIB REF

?.?

 

 

GEN L2-L3 V

#

CALIB REF

#.#

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

TP-6200 10/12

Local Programming Mode On

Section 2 Operation 121

Page 121