TP-6200 10/12100 Section 2 Operation Local Programming Mode On
Menu 9—Input Setup
Menu 9 Displays with Key Entries
MAIN MENU NUMBER 9
MENU 9
INPUT SETUP
Key
Entry Display Description
Input a menu number.
Displays the setup of digital auxiliary inputs heading.
Displays the digital input 01 with the user-defined description.
Note: Press the down arrow to move to the start of the next input
setup.
SETUP DIGITAL
AUXILIARY INPUTS
DIGITALINPUT 01
(USER DEFINED DESC)
Identifies the signal source for digital input 01. Use the menu down
key to select the digital input.
DIGITALINPUT 01
(see Group A) YES/NO
DIGITALINPUT 01
ENABLED YES/NO Displays the digital input 01, enabled yes or no selection.
Press the Enter key.
DIGITALINPUT 01
ENABLED YES
Confirms the entry.
DIGITALINPUT 01
ENABLED YES
OR
Press the Enter key.
DIGITALINPUT 01
ENABLED NO
Confirms the entry.
DIGITALINPUT 01
ENABLED NO
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
DIGITALINPUT 01
ENABLED NO Entering YES enables digital input 01.
Entering NO disables digital input 01.
DIGITALINPUT 01
ENABLED YES
GroupA
The preprogrammed
selections include the
following list. See
Appendix E for
application and
restrictions with specific
engines.
WARNING Y/N
SHUTDOWN TYPE A Y/N
SHUTDOWN TYPE B Y/N
VOLTAGERAISE Y/N
VOLTAGELOWER Y/N
GroupA, continued
VARPF MODE Y/N
REMOTE SHUTDOWN Y/N
REMOTE RESET Y/N
AIR DAMPER Y/N
LOW FUEL Y/N
FIELD OVERVOLTAGE Y/N
IDLE MODE ACTIVE Y/N
BATTLESWITCH Y/N
GROUND FAULT Y/N
BATCHGR FAULT Y/N
HIGH OIL TEMP Y/N
GroupA, continued
LOW COOLANT LEVEL Y/N
LOW COOLANT TEMP Y/N
BREAKER CLOSED Y/N
ENABLE SYNCH Y/N
AFM SHUTDOWN Y/N
KNOCK SHUTDOWN Y/N
DETON WARNING Y/N
DETON SHUTDOWN Y/N
LOW FUEL SHUTDOWN Y/N