Relay

 

 

Inhibit

 

 

Status Event

Refer

 

Driver

 

Default

Time

Time

User-Defined

to

 

Output

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Range Setting

Selection

(sec.)

(sec.)

Settings

Load Shed

10

LOAD SHED

RDO-30 ]]

80%--120%

100% of

 

2--10

 

kW Overload ]]

 

KW OVER

 

 

kW rating

 

 

 

 

 

 

 

 

with 5 sec.

 

 

 

 

 

 

 

 

delay

 

 

 

 

 

 

 

 

 

 

 

 

Load Shed Over

10

LOAD SHED

RDO only

 

 

 

 

Not adjustable

Temperature [[

 

OVER

 

 

 

 

 

 

(Activated by a High

 

TEMPERATURE

 

 

 

 

 

 

Coolant Temp.

 

 

 

 

 

 

 

 

shutdown)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load Shed

10

LOAD SHED

RDO-31 [

 

59 Hz

 

5

Not adjustable

Underfrequency [

 

UNDER

 

 

(60 Hz)

 

 

 

 

 

FREQUENCY

 

 

49 Hz

 

 

 

 

 

 

 

 

(50 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor

10

LOCKED

 

 

 

 

 

Not adjustable

Shutdown

 

ROTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loss of ECM

10

LOSS OF ECM

RDO-26 *

 

 

 

4

Not adjustable

Communication

 

COMM

 

 

 

 

 

 

(ECM only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loss of Field

10

SD LOSS OF

 

 

 

 

 

Not adjustable

Shutdown w

 

FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery Voltage

10

LOW BATTERY

RDO-12

10--12.5 V (12 V)

12 V (12 V)

0

10

 

 

 

VOLTAGE

(lead 62)

20--25 V (24 V)

24 V (24 V)

 

 

 

 

 

 

 

 

 

 

 

 

Low Coolant Level

 

 

 

 

 

 

 

(see D14) (with LCL

 

 

 

 

 

 

 

 

switch) **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Coolant

 

 

 

 

 

 

 

Temperature (see

 

 

 

 

 

 

 

 

D03) **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Coolant

10

LOW COOLANT

 

 

 

 

 

Not adjustable

Temperature

 

TEMP

 

 

 

 

 

 

Shutdown [[

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Fuel (Level or

 

 

 

 

 

 

 

Pressure) Warning

 

 

 

 

 

 

 

 

(see D02) **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Fuel Pressure

 

 

 

 

 

 

 

Shutdown (see D09)

 

 

 

 

 

 

 

 

(125RZG only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low) Oil Pressure

10

OIL

RDO-04

 

 

30

5

Not adjustable

Shutdown

 

PRESSURE

(lead 38)

 

 

 

 

 

 

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low) Oil Pressure

10

OIL

RDO-07

 

 

30

 

Not adjustable

Warning

 

PRESSURE

(lead 41)

 

 

 

 

 

 

 

WARNING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintenance Due

10

MAINTENANCE

 

 

 

 

 

Not adjustable

 

 

DUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master Not In Auto

10

MASTER NOT

RDO-09

 

 

 

 

Not adjustable

(Generator Set

 

IN AUTO

(lead 80)

 

 

 

 

 

Switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master Switch Error

10

MASTER

 

 

 

 

 

Not adjustable

 

 

SWITCH

 

 

 

 

 

 

 

 

ERROR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master Switch to Off

10

MASTER

 

 

 

 

 

Not adjustable

 

 

SWITCH TO

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master Switch Open

10

MASTER

 

 

 

 

 

Not adjustable

 

 

SWITCH OPEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NFPA 110 Fault **

10

NFPA 110

RDO-10

 

 

 

 

Not adjustable

 

 

FAULT

(lead 32)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Air Temperature

10

NO AIR TEMP

 

 

 

30

4

Not adjustable

Signal Warning ]

 

SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

**

NFPA applications

[

Non-paralleling applications

[[

DDC/MTU engine with MDEC/ADEC

]

Waukesha-powered models

]]

FAA only

w

Paralleling applications

 

 

TP-6200 10/12

Appendix 199

Page 199
Image 199
Kohler 20-3250 kW manual Load Shed, Switch to OFF