Relay

 

 

Inhibit

 

 

Status Event

Refer

 

Driver

 

Default

Time

Time

User-Defined

to

 

Output

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Range Setting

Selection

(sec.)

(sec.)

Settings

No Coolant

10

NO COOL

 

 

 

30

4

Not adjustable

Temperature Signal

 

TEMP SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Oil Pressure

10

NO OIL

 

 

 

30

4

Not adjustable

Signal

 

PRESSURE

 

 

 

 

 

 

 

 

SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Oil Temperature

10

NO OIL TEMP

 

 

 

30

4

Not adjustable

Signal Warning ]

 

SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overcrank Shutdown

8, 10

OVER CRANK

RDO-02

0--6 Cycles

3 Cycles

 

 

 

 

 

 

(lead 12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overcurrent

10

OVER

 

 

110%

 

10

Not adjustable

 

 

CURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over Current VR

10

SD OVER

 

 

 

 

 

Not adjustable

(voltage restraint)

 

CURRENT VR

 

 

 

 

 

 

Shutdown w

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overfrequency

7, 10

OVER

RDO-28

102%--140%

110% Std.

 

10

 

Shutdown

 

FREQUENCY

 

 

103% FAA

 

 

 

 

 

 

 

 

 

 

 

 

Over Power

10

SD OVER

 

 

102%

 

 

Not adjustable

Shutdown w

 

POWER

 

 

Stdby

 

 

 

 

 

 

 

 

112% Prime

 

 

 

 

 

 

 

 

 

 

 

 

Overspeed

7, 10

OVER SPEED

RDO-01

65--70 Hz (60 Hz)

70 (60 Hz)

 

0.25

 

Shutdown

 

 

(lead 39)

55--70 Hz (50 Hz)

70 (50 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

Overvoltage

7, 8,

OVER

RDO-20

105%--135%

115%

 

2--10

 

Shutdown

10

VOLTAGE

(lead 26)

of nominal

2-sec time

 

 

 

 

 

 

 

 

delay[

 

 

 

 

 

 

 

 

135%

 

 

 

 

 

 

 

 

10-sec time

 

 

 

 

 

 

 

 

delayw

 

 

 

 

 

 

 

 

 

 

 

 

Password

 

 

 

 

 

 

 

(see Access Code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pre Lube Relay ]

10

PRE LUBE

RDO-26 ]

 

 

 

4

Not adjustable

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Reset

 

 

 

 

 

 

 

(see D16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

 

 

 

 

 

 

(see D15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse Power

10

SD REVERSE

 

 

 

 

 

Not adjustable

Shutdown w

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Sensor Fault

10

SPEED

RDO-24

 

 

 

 

Not adjustable

 

 

SENSOR

 

 

 

 

 

 

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting Aid (see

 

 

 

 

 

 

 

Time Delay Starting

 

 

 

 

 

 

 

 

Aid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Ready

10

 

RDO-17

 

 

 

 

Not adjustable

 

 

 

(lead 60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Engine

8, 10

DELAY ENG

RDO-16

00:00--10:00

5:00

 

 

 

Cooldown (TDEC)

 

COOLDOWN

(lead 70C)

min:sec

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Engine

8, 10

DELAY ENG

 

00:00--5:00

00:01

 

 

 

Start (TDES)

 

START

 

min:sec

 

 

 

 

 

 

 

 

 

 

 

 

 

Time Delay Starting

8, 10

 

 

0--10 sec.

 

 

 

 

Aid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Underfrequency

7, 10

UNDER

RDO-29 ]

80%--97%

97% FAA

 

10

 

 

 

FREQUENCY

 

 

90%[

 

 

 

 

 

 

 

 

80%w

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

**

NFPA applications

[

Non-paralleling applications

[[

DDC/MTU engine with MDEC/ADEC

]

Waukesha-powered models

]]

FAA only

w

Paralleling applications

 

 

200 Appendix

TP-6200 10/12

Page 200
Image 200
Kohler 20-3250 kW manual No Cool, Current VR