2.7.11 Menu 11—Voltage Regulator

Menu 11 displays setup of the voltage regulator functions including line-to-line voltages, underfrequency unloading (volts per Hz), reactive droop, power factor, and kVAR adjustments.

The user must enable the programming mode to edit the display.

See Section 2.8.11 to make changes in this menu.

Note: The individual line-to-line voltages are displayed for review purposes only.

Note: Voltage regulator gain is used for adjusting voltage stability and/or response.

Note: Utility gain is used for VAR or PF stability adjust while paralleling to a utility.

Menu 11 Overview

MENU 11

VOLTAGE REGULATOR

AVG L-L V

# →

VOLT ADJ

?.?

 

 

 

 

 

 

UNDER FREQ UNLOAD

ENABLED

Y/N

 

 

 

 

 

REACTIVE DROOP

ENABLED

Y/N

 

L1-L2 VOLTS

 

#

 

 

 

 

 

 

 

 

FREQUENCY

# HZ→

 

SETPOINT

?.? HZ

 

 

 

 

.8 PF RATED LOAD

 

VOLTAGE DROOP

?.?%

L2-L3 VOLTS (3 PHASE)

#

 

 

 

 

 

SLOPE

?.? VOLTS-PER-CYCLE

 

L3-L1 VOLTS (3 PHASE)

#

 

 

 

VAR CONTROL

ENABLED

Y/N

 

 

 

 

 

 

 

 

 

PF CONTROL

ENABLED

Y/N

 

 

 

 

 

 

REGULATOR GAIN ADJ

 

GAIN

#

 

 

 

UTILITY GAIN ADJUST

 

GAIN

#

ANALOG VOLTAGE ADJUST

ENABLEDY/N

RESET REGULATOR

DEFAULTS?Y/N

TOTAL KVAR

# →

 

GENERATING/

Y/N→

KVAR ADJ

?.?

 

 

ABSORBING

Y/N

 

 

 

 

 

 

AVERAGE PF

# →

 

LAGGING/

Y/N→

PF ADJ

?.?

 

 

LEADING

Y/N

 

 

 

 

 

 

66 Section 2 Operation

TP-6200 10/12

Page 66
Image 66