System Monitoring LEDs and Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

Generator

 

 

Common

 

 

Fault

System

Running

Communication

Common

Fault

 

Fault and Status Condition

LED

Ready LED

LED

Status LED

Fault LED

Output

Horn

Overcrank Shutdown

Red

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

High Engine Temperature Warning *

Yellow

Red SF

Green

Green

Red SF

On

On

 

 

 

 

 

 

 

 

High Engine Temperature Shutdown

Red

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Low Oil Pressure Warning *

Yellow

Red SF

Green

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Low Oil Pressure Shutdown

Red

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Overspeed Shutdown

Red

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Emergency Stop *

Red

Red SF

Off

Green

Off

On

On

 

 

 

 

 

 

 

 

Low Coolant Level/Auxiliary Shutdown *

Red

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Low Coolant Temperature *

Yellow

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Low Fuel—Level or Pressure *

Yellow

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

EPS Supplying Load (RSA II)

Green

Green

Green or Off

Green

Off

Off

Off

 

 

 

 

 

 

 

 

System Ready

Green

Green

Green or Off

Green

Off

Off

Off

 

 

 

 

 

 

 

 

System Not Ready

Red

Red SF

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

Low Cranking Voltage

Yellow

Red SF

Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

(Loss of) Communication Status

Red

Off

Off

Red FF

Off

On

On

(Master RSA II)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Loss of) Communication Status (Slave RSA II)

Red

Off

Off

Red SF

Off

On

On

 

 

 

 

 

 

 

 

Not-In-Auto

Red

Red SF

Green or Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

Battery Charger Fault *

Yellow

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

High Battery Voltage *

Yellow

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

Low Battery Voltage *

Yellow

Green

Green or Off

Green

Off

Off

Off

 

 

 

 

 

 

 

 

User Input #1 (RSA II) Warning

Yellow

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

User Input #1 (RSA II) Shutdown

Red

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

User Input #2 (RSA II) Warning

Yellow

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

User Input #2 (RSA II) Shutdown

Red

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

User Input #3 (RSA II) Warning

Yellow

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

User Input #3 (RSA II) Shutdown

Red

Green

Green or Off

Green

Off

On

On

 

 

 

 

 

 

 

 

Common Fault Warning

Yellow

Green

Green or Off

Green

Red SF

On

Off

 

 

 

 

 

 

 

 

Common Fault Shutdown

Red

Green

Green or Off

Green

Red SF

On

On

 

 

 

 

 

 

 

 

ATS Position N (RSA II with ATS only)

Green

Green

Green or Off

Green

Off

Off

Off

 

 

 

 

 

 

 

 

ATS Position E (RSA II with ATS only)

Red

Red SF

Green or Off

Green

Off

Off

On

 

 

 

 

 

 

 

 

ATS Available N (RSA II with ATS only)

Green

Green

Green or Off

Green

Off

Off

Off

 

 

 

 

 

 

 

 

ATS Available E (RSA II with ATS only)

Red

Red SF

Green or Off

Green

Off

Off

On

 

 

 

 

 

 

 

 

ATS Fault (RSA II with ATS only)

Yellow

Yellow

Green or Off

Green

Off

Off

On

 

 

 

 

 

 

 

 

ATS Fault (RSA II with ATS only)

Red

Red SF

Green or Off

Green

Off

Off

On

 

 

 

 

 

 

 

 

SF = Slow Flash (1 second intervals), FF = Fast Flash (200 ms intervals)

* May require optional kit or user-provided device to enable function and LED indication.

Figure 6-20 System Monitoring LEDs and Functions