TP-6200 10/12 171Section6 Accessories
g. Press to enter the inhibit time. Entry
Accepted is displayed and the inhibit time 0:00
is now displayed.
h. Press to display Digital Input #06 Delay
TIme.
i. Press to enter delay time. Entry
Accepted is displayed. Default delay time is
5 sec.
j. Press .
7. Verify Programming.
a. Move handle of ground fault circuit breaker at
generator set to simulate a ground fault.
b. Verify that display shows D06 Ground Fault.
The System Warning LED should be
illuminatedand the alarm horn should sound. If
these indicators are not present, recheck steps
6a. through 6j.
c. Return handle of ground fault circuit breaker to
the non-ground fault position. D06 Ground
Fault display should now be cleared.
8. Set Programming Mode to Off.
a. Press .
b. Presskey until Programming Mode Off is
displayed.
c. Press the YES key .
d. When the Enter Code displays, press the
factory default or the user password
keys and . The programming mode LED
should now be off.
9. Place the controller master switch to the OFF/
RESET position.
10. Disconnect the battery negative (--) lead to power
down the generator set.
11. After 2-3 minutes, reconnect the battery negative
(--)lead.
12. Reset the controller clock. See Menu 6—Time and
Date.
6.1.6 Idle (Speed) Mode Feature
The idle (speed) mode feature provides the ability to
start and run the engine at idle (reduced) speed for a
selectable time period (0--10minutes) during warm-up.
The controller will override the idle speed mode if the
engine reaches the preprogrammed engine warmed-up
temperature before the idle mode times out. See
Figure 6-9 for user-supplied switch connection.
GM16088A-A
Figure 6-9 Idle (Speed) Mode Switch