g.Press to enter the inhibit time. Entry Accepted is displayed and the inhibit time 0:00 is now displayed.
h.Press to display Digital Input #06 Delay TIme.
i.Press to enter delay time. Entry Accepted is displayed. Default delay time is 5 sec.
j.Press .
7.Verify Programming.
a.Move handle of ground fault circuit breaker at generator set to simulate a ground fault.
b.Verify that display shows D06 Ground Fault. The System Warning LED should be illuminated and the alarm horn should sound. If these indicators are not present, recheck steps 6a. through 6j.
c.Return handle of ground fault circuit breaker to the
8.Set Programming Mode to Off.
a.Press .
b.Press key until Programming Mode Off is displayed.
c.Press the YES key .
d.When the Enter Code displays, press the
factory default or the user password
keys and . The programming mode LED should now be off.
9.Place the controller master switch to the OFF/ RESET position.
10.Disconnect the battery negative
11.After
12.Reset the controller clock. See Menu
6.1.6Idle (Speed) Mode Feature
The idle (speed) mode feature provides the ability to start and run the engine at idle (reduced) speed for a selectable time period
Figure 6-9 Idle (Speed) Mode Switch
Section 6 Accessories 171 |