Carrier 40QA024-060 specifications Control Circuit Connections Arrangement

Models: 40QA024-060

1 24
Download 24 pages 43.12 Kb
Page 13
Image 13
Fig. 17 — Control Circuit Connections Arrangement

Step 8 — Make Connections Between Indoor and Outdoor Units — The thermostat is wired between the indoor and outdoor units to make the system complete.

CHECK ACCURATER METERING DEVICE — The cor- rect AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device (see Fig. 19) is supplied with the outdoor unit. Refer to Tables 4A-4C to determine the correct AccuRater piston size and charge combination required for the condenser/evaporator system being installed.

Piston style as shown in Fig. 19 is shipped with the unit. Do not interchange components between the AccuRater device types.

COOLING ONLY SYSTEMS — The following connec- tions must be made to the outdoor unit for it to operate as a sys- tem with the indoor unit:

Route 2 wires of field-supplied 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage terminal block of the fan coil unit and the blue and brown low-voltage wires in the outdoor unit low voltage terminal block. Connect the wires Y1 to Y and C to C. See Fig. 19.

HEAT PUMP SYSTEMS — The following connections must be made to the outdoor unit for it to operate as a system with the indoor unit:

Route 5 wires of field-supplied 18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil and the outdoor unit low-voltage terminal block. Connect Y1 to Y, R to R, O to O, W2 to W2, and C to C with the wires. See Fig. 20.

The heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed de- frost is factory set for 90 minutes.

 

 

 

LEGEND

ASM

Air Sweep Motor

NEC

National Electrical Code

ASR

Air Sweep Relay

PL

Plug

EQUIP GND

Equipment Ground

TB

Terminal Board

FL

Fuse Link

TRAN

Transformer

FPT

Freeze Protection Thermostat

 

Terminal (Marked)

HP

Heat Pump

 

 

 

HR

Heater Relay

 

Terminal (Unmarked)

HTR

Heater

 

Splice

HTT

Heater Temp. Thermostat

 

 

 

IFM

Indoor-Fan Motor

 

 

NOTES:

1.If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.

2.Wire in accordance with NEC and local codes.

3.Transformer is thermally protected and will reset automatically.

4.Indoor-fan motor(s) are inherently thermally protected.

Fig. 17 — Control Circuit Connections Arrangement

Terminal Block

Factory Wiring Field Power Wiring Field Control Wiring Printed Circuit Board Accessory or Optional Wiring

13

Page 13
Image 13
Carrier 40QA024-060 specifications Control Circuit Connections Arrangement