Step 8 — Make Connections Between Indoor and Outdoor Units — The thermostat is wired between the indoor and outdoor units to make the system complete.
CHECK ACCURATER METERING DEVICE — The cor- rect AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device (see Fig. 19) is supplied with the outdoor unit. Refer to Tables
Piston style as shown in Fig. 19 is shipped with the unit. Do not interchange components between the AccuRater device types.
COOLING ONLY SYSTEMS — The following connec- tions must be made to the outdoor unit for it to operate as a sys- tem with the indoor unit:
Route 2 wires of
HEAT PUMP SYSTEMS — The following connections must be made to the outdoor unit for it to operate as a system with the indoor unit:
Route 5 wires of
The heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed de- frost is factory set for 90 minutes.
|
|
| LEGEND |
ASM | — Air Sweep Motor | NEC | — National Electrical Code |
ASR | — Air Sweep Relay | PL | — Plug |
EQUIP GND | — Equipment Ground | TB | — Terminal Board |
FL | — Fuse Link | TRAN | — Transformer |
FPT | — Freeze Protection Thermostat |
| Terminal (Marked) |
HP | — Heat Pump |
| |
|
| ||
HR | — Heater Relay |
| Terminal (Unmarked) |
HTR | — Heater |
| Splice |
HTT | — Heater Temp. Thermostat |
| |
|
| ||
IFM | — |
|
|
NOTES:
1.If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2.Wire in accordance with NEC and local codes.
3.Transformer is thermally protected and will reset automatically.
4.
Fig. 17 — Control Circuit Connections Arrangement
Terminal Block
Factory Wiring Field Power Wiring Field Control Wiring Printed Circuit Board Accessory or Optional Wiring
13