f.Refer to the outdoor unit Installation,
g.Install a
3.Insulate and caulk wall openings to reduce air infiltra- tion and refrigerant pipe vibrations on structure.
4.Evacuate piping, if necessary. If either refrigerant pip- ing or the indoor coil is exposed to atmospheric condi- tions, it must be evacuated to 1000 microns to eliminate contamination and moisture in the system.
Step 5 — Connect Condensate Drain Line —
Observe all local sanitary codes when installing condensate drains. Refer to Fig. 3 and 14 for drain pipe connection from indoor unit.
1.Use hard polyvinyl chloride (PVC) pipe material with nominal ID of 3/4 in. to connect at drain line. Use pipe insulation
2.To ensure regular flow of condensate water, the drain pipe should be pitched toward an open drain or sump at a downward slope of at least
3.Attach plate with screws under piping hole.
4.Attach drain pipe with nylon wire tie passing through hole (Fig. 15).
NOTE: Do not fasten nylon wire ties tight enough to deform the insulation, as this affects its performance.
5.Insulate condensate drain line(s) that are located in or above an occupied area with a
6.Install an external trap at the end of the condensate line.
NOTE: Should the installation require one, a conden- sate pump may be ordered as a
Table 4A — Piston and Charge Combinations — Cooling Only Systems
COOLING | OUTDOOR UNIT | PISTON | CHARGE (lb) | |
INDOOR UNIT SIZE | 38HDR | SIZE | ||
| ||||
024 | 018 | 57 | 7.0 | |
024 | 57 | 7.75 | ||
| ||||
036 | 030 | 65 | 10.1 | |
036 | 70 | 8.9 | ||
| ||||
048 | 048 | 80 | 12.2 | |
060 | 060 | 90 | 12.5 |
Table 4B — Piston and Charge Combinations — Heat Pump Systems
HEAT PUMP | OUTDOOR UNIT | PISTON SIZE | PISTON SIZE | CHARGE (lb) | |
INDOOR UNIT SIZE | 38QRR | INDOOR | OUTDOOR | ||
| |||||
024 | 018 | 49 | 40 | 7.5 | |
024 | 55 | 43 | 7.8 | ||
| |||||
036 | 030 | 65 | 55 | 12 | |
036 | 70 | 63 | 13 | ||
| |||||
048 | 048 | 82 | 73 | 12.2 | |
060 | 060 | 80 | 12.8 |
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
Table 4C — Piston and Charge Combinations — Heat and Cool Systems
HEAT PUMP | OUTDOOR UNIT | PISTON | CHARGE (lb) | |
INDOOR UNIT SIZE | 38HDR | SIZE | ||
| ||||
024 | 018 | 57 | 7.0 | |
024 | 57 | 7.75 | ||
| ||||
036 | 030 | 65 | 10.1 | |
036 | 70 | 8.9 | ||
| ||||
048 | 048 | 80 | 12.2 | |
060 | 060 | 12.5 |
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
8