Carrier 40QA024-060 specifications AccuRater Bypass Type, Metering Device Components

Models: 40QA024-060

1 24
Download 24 pages 43.12 Kb
Page 15
Image 15
Fig. 19 — AccuRater (Bypass Type)

Step 8 — Make Connections Between Indoor and Outdoor Units — The thermostat is wired between the indoor and outdoor units to make the system complete.

CHECK ACCURATER METERING DEVICE — The cor- rect AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device (see Fig. 19) is supplied with the outdoor unit. Refer to Tables 4A-4C to determine the correct AccuRater piston size and charge combination required for the condenser/evaporator system being installed.

Piston style as shown in Fig. 19 is shipped with the unit. Do not interchange components between the AccuRater device types.

COOLING ONLY SYSTEMS — The following connec- tions must be made to the outdoor unit for it to operate as a sys- tem with the indoor unit:

Route 2 wires of field-supplied 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage terminal block of the fan coil unit and the blue and brown low-voltage wires in the outdoor unit low voltage terminal block. Connect the wires Y1 to Y and C to C. See Fig. 20.

HEAT PUMP SYSTEMS — The following connections must be made to the outdoor unit for it to operate as a system with the indoor unit:

Route 5 wires of field-supplied 18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil and the outdoor unit low-voltage terminal block. Connect Y1 to Y, R to R, O to O, W2 to W2, and C to C with the wires. See Fig. 21.

The heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed de- frost is factory set for 90 minutes.

38HDR018-060

38QRR018-060

Fig. 19 — AccuRater (Bypass Type)

Metering Device Components

15

Page 15
Image 15
Carrier 40QA024-060 specifications AccuRater Bypass Type, Metering Device Components