Table 35—Fan Performance 48HJ007 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

913

0.64

569

1010

0.80

715

1098

0.98

869

1178

1.16

1032

1252

1.35

1203

1900

952

0.73

652

1046

0.91

805

1131

1.09

965

1210

1.28

1134

1282

1.48

1311

2000

992

0.84

744

1083

1.02

903

1166

1.21

1070

1242

1.40

1245

1313

1.61

1427

2100

1032

0.95

844

1120

1.14

1010

1200

1.33

1184

1275

1.54

1365

1345

1.75

1553

2200

1073

1.07

954

1158

1.27

1127

1236

1.47

1307

1308

1.68

1495

1377

1.90

1689

2300

1114

1.21

1074

1196

1.41

1254

1272

1.62

1440

1343

1.84

1634

1409

2.07

1834

2400

1155

1.36

1204

1234

1.57

1391

1308

1.78

1584

1377

2.01

1784

1443

2.24

1990

2500

1196

1.51

1345

1273

1.73

1538

1345

1.96

1738

1412

2.19

1945

1477

2.43

2157

2600

1238

1.69

1497

1312

1.91

1697

1382

2.14

1904

1448

2.38

2117

1511

2.63

2335

2700

1280

1.87

1660

1352

2.10

1867

1420

2.34

2081

1484

2.59

2300

1546

2.84

2526

2800

1322

2.07

1835

1392

2.31

2050

1458

2.56

2270

1521

2.81

2496

2900

1364

2.28

2023

1432

2.53

2245

1496

2.78

2472

3000

1406

2.50

2224

1472

2.76

2452

 

AIRFLOW

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

1.2

 

 

 

 

1.4

 

 

 

 

 

1.6

 

 

 

 

 

1.8

 

 

 

 

 

2.0

 

 

 

 

Rpm

Bhp

Watts

 

Rpm

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

Rpm

 

Bhp

Watts

 

Rpm

 

Bhp

 

Watts

 

1800

1322

1.56

1382

 

1388

1.77

1568

 

1451

 

1.98

 

1762

1510

 

2.21

1962

1568

 

2.44

 

2169

 

 

1900

1351

1.68

1495

 

1416

1.90

1686

 

1477

 

2.12

 

1885

1536

 

2.35

2090

1593

 

2.59

 

2302

 

 

2000

1380

1.82

1617

 

1444

2.04

1814

 

1505

 

2.27

 

2017

1563

 

2.51

2227

1619

 

2.75

 

2443

 

 

2100

1411

1.97

1748

 

1473

2.20

1950

 

1533

 

2.43

 

2159

1590

 

2.67

2374

 

 

 

 

2200

1441

2.13

1890

 

1503

2.36

2097

 

1562

 

2.60

 

2311

1618

 

2.85

2532

 

 

 

 

2300

1473

2.30

2041

 

1533

2.54

2254

 

1591

 

2.79

 

2474

 

 

 

 

 

 

2400

1505

2.48

2203

 

1564

2.73

2422

 

 

 

 

 

 

 

 

 

2500

1537

2.68

2376

 

 

 

 

 

 

 

 

 

 

 

2600

1571

2.88

2560

 

 

 

 

 

 

 

 

 

 

 

2700

 

 

 

 

 

 

 

 

 

 

 

2800

 

 

 

 

 

 

 

 

 

 

 

2900

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Grey cells indicate field-supplied drive is required.

 

 

 

 

 

 

Bhp — Brake Horsepower

 

 

 

 

 

 

 

 

 

 

 

 

2. Maximum continuous bhp is 2.90.

 

 

 

 

 

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

 

 

 

 

 

 

3. See general fan performance notes.

 

 

 

 

 

 

 

 

 

*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.

 

 

 

Table 36—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPONENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1250

 

1500

 

 

1750

2000

 

2250

 

2500

 

2750

 

 

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical EconoMi$er2 and EconoMi$er IV

 

 

0.045

 

0.065

 

 

0.08

0.12

 

0.145

 

0.175

 

0.22

 

 

 

0.255

 

 

Horizontal EconoMi$er2 and EconoMi$er IV

 

 

 

 

 

0.1

0.125

 

0.15

 

 

0.18

 

0.225

 

 

0.275

 

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Perfor- mance tables to determine indoor blower rpm and watts.

44