Carrier 48HE003---006, 48HJ004---007 48HE,HJ, Flue Hood Details, Gas Piping Guide With Accessory

Models: 48HJ004---007 48HE003---006

1 64
Download 64 pages 9.08 Kb
Page 8
Image 8
Fig. 10 ---Flue Hood Details

C06114

Fig. 10 ---Flue Hood Details

48HE,HJ

LEGEND

NFGC — National Fuel Gas Code *Field supplied.

NOTE: Follow all local codes.

SPACING OF SUPPORTS

STEEL PIPE

SPACING OF SUPPORTS

NOMINAL DIAMETER (in.)

X DIMENSION (ft)

1/2

6

3/4 or 1

8

11/4 or larger

10

C06115

Fig. 11 ---Gas Piping Guide (With Accessory

Thru-the-Curb Service Connections)

Step 7 Make Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground.

field power supply

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.

Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local requirements.

Install conduit through side panel openings indicated in Fig. 8. Route power lines through connector to terminal connections as shown in Fig. 12.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 3 and 4). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 3 and 4, Note 3 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes. (See Fig. 2.)

field control wiring

Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 13 and 14).

Connect thermostat wires to matching screw terminals of low-voltage connection board. (See Fig. 13 and 14.)

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. (See Fig. 15). The raceway provides the UL required clearance between high and low-voltage wiring.

heat anticipator settings

Set heat anticipator settings at 0.14 amp for first stage and 0.14 for second stage heating, when available.

8

Page 8
Image 8
Carrier 48HE003---006 48HE,HJ, Flue Hood Details, Gas Piping Guide With Accessory, Thru-the-CurbService Connections