Carrier 48HE003---006, 48HJ004---007 48HE,HJ, Cooling Charging Chart, 48HJ005 with

Models: 48HJ004---007 48HE003---006

1 64
Download 64 pages 9.08 Kb
Page 54
Image 54
Fig. 66 ---Cooling Charging Chart, 48HJ005 with

The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooling/reheat dehumidification coil. A tap is provided on the unit to measure liquid pressure entering the subcooling/reheat dehumidification coil.

IMPORTANT: The subcooling mode charging charts (Fig. 64-67) are to be used ONLY with units having the Humidi-MiZer adaptive dehumidification system. DO NOT use standard charge (Fig. 60-63) for units with Humidi-MiZer system, and DO NOT use Fig. 64-67 for standard units.

48HE,HJ

C06145

Fig. 66 ---Cooling Charging Chart, 48HJ005 with

Optional Humidi-MiZer Adaptive Dehumidification System

C06146

Fig. 67 ---Cooling Charging Chart, 48HJ007 with

Optional Humidi-MiZer Adaptive Dehumidification System

TO USE COOLING CHARGING CHART, STANDARD UNIT

Take the outdoor ambient temperature and read the suction pressure gauge. Refer to charts to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.

Example (Fig. 59):

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . 75°F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . 48°F (Suction temperature may vary ± 5°F.)

If a charging device is used, temperature and pressure readings must be accomplished using the charging charts.

54