Carrier 48HJ004---007, 48HE003---006 installation instructions 48HE,HJ, PhysicalData 48HJ

Models: 48HJ004---007 48HE003---006

1 64
Download 64 pages 9.08 Kb
Page 9
Image 9
Table 1—Physical Data 48HJ

Table 1—Physical Data 48HJ

BASE UNIT 48HJ

 

HJE/F/H/K/M/N004

HJD/E/F/G/H/K/L/M/N005

 

HJD/E/F/G/H/K/L/M/N006

HJD/E/F007

NOMINAL CAPACITY

 

3

4

 

5

6

OPERATING WEIGHT (lb)

 

 

 

 

 

 

Unit

 

530

540

 

560

635

Humidi-MiZerAdaptive Dehumidification System

15

23

 

25

29

EconoMi$er IV

 

50

50

 

50

50

Roof Curb

 

115

115

 

115

115

COMPRESSOR

 

 

Scroll

 

 

Quantity

 

1

1

 

1

1

Oil (oz)

 

42

53

 

50

60

REFRIGERANT TYPE

 

 

R-22

 

 

Expansion Device

 

 

AcutrolMetering Device

 

Operating Charge (lb-oz)

 

 

 

 

 

 

Standard Unit

 

5-8

10-2

 

10-0

12- 8

Unit With Humidi-Mizer Adaptive Dehumidification System

12-5

18-8

 

20-5

23-14

CONDENSER FAN

 

 

Propeller

 

 

Quantity...Diameter (in.)

 

1...22

1...22

 

1...22

1...22

Nominal Cfm

 

3500

3500

 

4100

4100

Motor Hp...Rpm

 

1/ ...825

1/ ...825

 

1/ ...1100

1/ ...1100

Watts Input (Total)

 

4

4

 

4

4

 

180

180

 

320

320

CONDENSER COIL

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

Rows...Fins/in.

 

1...17

2...17

 

2...17

2...17

Total Face Area (sq ft)

 

14.6

16.5

 

16.5

21.3

EVAPORATOR COIL

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

 

Standard Unit

 

 

 

 

 

 

Rows...Fins/in.

 

2...15

2...15

 

4...15

4...15

Total Face Area (sq ft)

 

5.5

5.5

 

5.5

7.3

Unit with Humidi-Mizer Adaptive Dehumidification System

 

 

 

 

 

Rows...Fins/in.

 

1...17

2...17

 

2...17

2...17

Total Face Area (sq ft)

 

3.9

3.9

 

3.9

5.2

EVAPORATOR FAN

 

 

Centrifugal Type, Belt Drive

 

Quantity...Size (in.)

 

1...10 x 10

1...10 x 10

 

1...10 x 10

1...10 x 10

Nominal Cfm

Std

1200

1600

 

2000

2400

Maximum Continuous Bhp

1.20

1.20

 

1.30/2.40*

2.40

 

Hi-Static

2.40

2.40

 

2.90

2.90

Motor RPM

Std

1620

1620

 

1725

1725

 

Hi-Static

1725

1725

 

1725

1725

Motor Frame Size

Std

48

48

 

48/56*

56

 

Hi-Static

56

56

 

56

56

Fan Rpm Range

Std

680-1044

770-1185

 

1035-1460

1119-1585

Motor Bearing Type

Hi-Static

1075-1455

1075-1455

 

1300-1685

1300-1685

 

Ball

Ball

 

Ball

Ball

Maximum Fan Rpm

Std

2100

2100

 

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

1.9/2.9

1.9/2.0

 

2.4/3.4

2.4/3.4

 

Hi-Static

2.8/3.8

2.8/3.8

 

3.4/4.4

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1/2

1/2

 

5/8

5/8

 

Hi-Static

5/8

5/8

 

5/8

7/8

Fan Pulley Pitch Diameter (in.)

Std

4.5

4.0

 

4.0

4.0

 

Hi-Static

4.5

4.0

 

4.5

4.5

Belt — Type...Length (in.)

Std

1...A...36

1...A...36

 

1....4...40

1...A...38

Pulley Center Line Distance (in.)

Hi-Static

1...A...39

1...A...39

 

1...A...40

1...A...40

Std

10.0-12.4

10.0-12.4

 

14.7-15.5

14.7-15.5

Speed Change per Full Turn of

65

70

 

75

95

Movable Pulley Flange (rpm)

Hi-Static

65

65

 

60

60

Movable Pulley Maximum Full

Std

5

5

 

6

5

Turns from Closed Position

Hi-Static

6

6

 

5

5

Factory Setting — Full Turns Open

Std

3

3

 

3

3

 

Hi-Static

31/2

31/2

 

31/2

31/2

Factory Speed Setting (rpm)

Std

826

936

 

1248

1305

Fan Shaft Diameter at Pulley (in.)

Hi-Static

1233

1233

 

1396

1396

 

5/8

5/8

 

5/8

5/8

LEGEND

 

 

 

 

 

 

Bhp — Brake Horsepower

 

 

 

 

 

 

*Single phase/three phase.

 

 

 

 

 

 

†Indicates automatic reset.

 

120,000

 

 

 

 

**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and

 

 

 

 

Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000

 

 

 

 

Btuh Heat input units have 3 burners.

 

 

 

 

 

 

††An LP kit is available as an accessory. Kit may be used at elevations as high as 2000

 

 

 

 

ft. If an LP kit is used with Low NOx units, the Low NOx baffle must be removed and

 

 

 

 

the units will no longer be classified as Low NOx units.

 

 

 

 

 

ll Three-phase standard models have heating inputs as shown. Single-phase stan-

 

 

 

 

dard models have one-stage heating with heating input values as follows:

 

 

 

 

 

HJD005-006,HJE004 — 72,000 Btuh

 

 

 

 

 

 

HJE005-006,HJF004 — 115,000 Btuh

 

 

 

 

 

HJF005-006 — 150,000 Btuh

 

 

 

 

 

 

***California compliant three-phase models.

 

 

 

 

 

†††California SCAQMD compliant low NOx

models have combustion products that are

 

 

 

 

controlled to 40 nanograms per joule or less.

 

 

 

 

 

48HE,HJ