Carrier 48HJ004---007, 48HE003---006 48HE,HJ, Roof Curb Alignment, Property Damage Hazard

Models: 48HJ004---007 48HE003---006

1 64
Download 64 pages 9.08 Kb
Page 5
Image 5
Fig. 6 ---

C06111

 

 

 

 

Fig. 6 ---

Rigging Details

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

OPERATING

 

 

 

 

DIMENSIONS

 

 

 

 

WEIGHT

“A”

 

 

 

“B”

 

“C”

48HE

 

 

 

 

 

lb

 

kg

in.

 

mm

 

in.

 

mm

in.

 

mm

 

 

 

 

 

 

003

530

 

240

73.69

 

1872

 

35.50

 

902

33.31

 

847

004

540

 

245

73.69

 

1872

 

35.50

 

902

33.31

 

847

005

560

 

254

73.69

 

1872

 

35.50

 

902

33.31

 

847

006

635

 

288

73.69

 

1872

 

35.50

 

902

33.31

 

847

UNIT

OPERATING

 

 

 

 

DIMENSIONS

 

 

 

 

WEIGHT

“A”

 

 

 

“B”

 

“C”

48HJ

 

 

 

 

 

lb

 

kg

in.

 

mm

 

in.

 

mm

in.

 

mm

 

 

 

 

 

 

004

530

 

240

73.69

 

1872

 

35.50

 

902

33.31

 

847

005

540

 

245

73.69

 

1872

 

35.50

 

902

33.31

 

847

006

560

 

254

73.69

 

1872

 

35.50

 

902

33.31

 

847

007

635

 

288

73.69

 

1872

 

35.50

 

902

33.31

 

847

48HE,HJ

C06208

Fig. 7 ---Roof Curb Alignment

Support gas piping as shown in the table in Fig. 11. For example, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.

!WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal injury, death and property damage.

All panels must be in place when rigging and lifting.

See Fig. 11 for typical pipe guide and locations of external manual gas shutoff valve.

NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.

!WARNING

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.

5

Page 5
Image 5
Carrier 48HJ004---007, 48HE003---006 48HE,HJ, Roof Curb Alignment, Property Damage Hazard, Fire, Explosion Hazard