48HE,HJ
2.Turn off power to the unit and tag disconnect.
3.Reverse any two of the unit power leads.
4.Turn on power to the unit and energize the compressor.
The suction and discharge pressure levels should now move to their normal
NOTE: When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.
Step 10 —Cooling
Set the space thermostat to the OFF position. Set the system selector switch at COOL position and the fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor starts when contactor closes.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The compressor will shut off. Evaporator fan will shut off after a
To Shut Off Unit - Set the system selector switch at OFF position. Resetting the thermostat at a position above room temperature shuts off the unit temporarily until the space temperature exceeds the thermostat setting. Units are equipped with a
Step 11 —Main Burners
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move thermostat set point above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, then lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off.
Refer to Tables 37 and 38 for the correct orifice to use at high altitudes.
Table 37—Altitude Compensation*
48HJ004-007, 48HE003-006 Standard Units
| 72,000 AND | 150,000 BTUH | |||
| 115,000 BTUH | ||||
| NOMINAL INPUT | ||||
ELEVATION | NOMINAL INPUT | ||||
|
| ||||
(ft) | Natural | Liquid | Natural | Liquid | |
Gas | Propane | Gas | Propane | ||
| |||||
| Orifice | Orifice | Orifice | Orifice | |
| Size† | Size† | Size† | Size† | |
33 | 43 | 30 | 37 | ||
2,000 | 36 | 44 | 31 | 39 | |
3,000 | 36 | 45 | 31 | 40 | |
4,000 | 37 | 45 | 32 | 41 | |
5,000 | 38 | 46 | 32 | 42 | |
6,000 | 40 | 47 | 34 | 43 | |
7,000 | 41 | 48 | 35 | 43 | |
8,000 | 42 | 49 | 36 | 44 | |
9,000 | 43 | 50 | 37 | 45 | |
10,000 | 44 | 50 | 39 | 46 | |
11,000 | 45 | 51 | 41 | 47 | |
12,000 | 46 | 52 | 42 | 48 | |
13,000 | 47 | 52 | 43 | 49 | |
14,000 | 48 | 53 | 44 | 50 |
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher alti- tudes.
†Orifices available through your Carrier distributor.
Table 38—Altitude Compensation* —
48HJ004-006, 48HE003-006 Low NOx Units
| 60,000 AND | 120,000 BTUH | |||
| 90,000 BTUH | ||||
| NOMINAL INPUT | ||||
| NOMINAL INPUT | ||||
ELEVATION |
|
| |||
(ft) | Natural | Liquid | Natural | Liquid | |
Gas | Propane | Gas | Propane | ||
| |||||
| Orifice | Orifice | Orifice | Orifice | |
| Size† | Size† | Size | Size† | |
38 | 45 | 32 | 42 | ||
2,000 | 40 | 47 | 33 | 43 | |
3,000 | 41 | 48 | 35 | 43 | |
4,000 | 42 | 49 | 36 | 44 | |
5,000 | 43 | 49 | 37 | 45 | |
6,000 | 43 | 50 | 38 | 45 | |
7,000 | 44 | 50 | 39 | 46 | |
8,000 | 45 | 51 | 41 | 47 | |
9,000 | 46 | 52 | 42 | 48 | |
10,000 | 47 | 52 | 43 | 49 | |
11,000 | 48 | 53 | 44 | 50 | |
12,000 | 49 | 53 | 44 | 51 | |
13,000 | 50 | 54 | 46 | 52 | |
14,000 | 51 | 54 | 47 | 52 |
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher alti- tudes.
†Orifices are available through your local Carrier distributor.
Step 12 —Heating
1.Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2.Turn on electrical supply and manual gas valve.
3.Set system switch selector at HEAT position and fan switch at AUTO or ON position. Set heating temperature lever above room temperature.
4.The
5.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a
6.The
7.The
8.Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the
If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the
The
46