Table 9 — Fan Performance — 50TJ020 and 024

50TJ020, 024 (18 and 20 TONS)*

Airflow

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

0.4

 

 

 

 

 

0.6

 

 

 

 

0.8

 

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

682

 

1.99

 

1675

 

760

 

2.29

 

1922

 

832

 

2.59

2177

901

2.90

2441

965

3.22

2712

1027

3.56

2990

6,000

730

 

2.38

 

2005

 

802

 

2.68

 

2257

 

871

 

2.99

2516

935

3.31

2783

997

3.63

3057

1056

3.97

3337

6,500

778

 

2.82

 

2373

 

846

 

3.13

 

2630

 

911

 

3.44

2893

972

3.76

3164

1031

4.09

3440

1087

4.43

3722

7,000

828

 

3.31

 

2780

 

892

 

3.62

 

3042

 

953

 

3.94

3310

1011

4.26

3583

1067

4.59

3863

1121

4.93

4148

7,500

878

 

3.84

 

3227

 

938

 

4.15

 

3494

 

996

 

4.48

3766

1051

4.81

4043

1105

5.14

4326

1156

5.49

4613

8,000

928

 

4.42

 

3715

 

985

 

4.74

 

3986

 

1040

 

5.07

4263

1093

5.40

4544

1144

5.74

4830

1194

6.09

5120

8,500

979

 

5.05

 

4245

 

1033

 

5.38

 

4521

 

1085

 

5.71

4801

1136

6.05

5086

1185

6.39

5375

1232

6.74

5669

9,000

1030

 

5.73

 

4817

 

1082

 

6.06

 

5098

 

1131

 

6.40

5382

1180

6.74

5671

1227

7.09

5964

1272

7.44

6260

9,500

1082

 

6.46

 

5433

 

1131

 

6.80

 

5718

 

1178

 

7.14

6007

1225

7.49

6299

1270

7.84

6595

1313

8.20

6895

10,000

1134

 

7.25

 

6093

 

1180

 

7.59

 

6382

 

1226

 

7.94

6675

1270

8.29

6971

1313

8.65

7271

1356

9.01

7574

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50TJ020, 024 (18 and 20 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

 

 

1.6

 

 

 

 

 

1.8

 

 

 

 

1.9

 

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

 

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

Rpm

Bhp

Watts

 

 

 

5,500

1086

 

3.89

 

3275

 

1142

 

4.24

 

3567

 

1197

 

4.59

 

3864

 

1223

 

4.77

 

4015

1249

4.96

4167

 

 

 

6,000

1112

 

4.31

 

3623

 

1167

 

4.66

 

3915

 

1219

 

5.01

 

4213

 

1245

 

5.19

 

4364

1270

5.37

4516

 

 

 

6,500

1142

 

4.77

 

4010

 

1194

 

5.12

 

4304

 

1245

 

5.47

 

4602

 

1270

 

5.65

 

4754

1294

5.83

4906

 

 

 

7,000

1173

 

5.28

 

4438

 

1224

 

5.63

 

4733

 

1273

 

5.98

 

5033

 

1296

 

6.17

 

5184

1320

6.35

5337

 

 

 

7,500

1207

 

5.83

 

4906

 

1255

 

6.19

 

5203

 

1302

 

6.55

 

5504

 

1326

 

6.73

 

5657

1348

6.91

5810

 

 

 

8,000

1242

 

6.44

 

5415

 

1289

 

6.80

 

5714

 

1334

 

7.16

 

6018

 

1357

 

7.34

 

6171

1379

7.52

6325

 

 

 

8,500

1279

 

7.10

 

5966

 

1324

 

7.45

 

6268

 

1368

 

7.82

 

6573

 

1389

 

8.00

 

6728

1411

8.18

6883

 

 

 

9,000

1317

 

7.80

 

6561

 

1360

 

8.16

 

6865

 

1403

 

8.53

 

7173

 

1424

 

8.71

 

7328

1445

8.90

7484

 

 

 

9,500

1356

 

8.56

 

7198

 

1398

 

8.93

 

7505

 

1440

 

9.29

 

7815

 

1460

 

9.48

 

7972

1480

9.67

8129

 

 

 

10,000

1397

 

9.37

 

7881

 

1438

 

9.74

 

8190

 

1477

 

10.11

 

8503

 

 

 

 

 

 

 

LEGEND

Bhp —

Brake Horsepower

FIOP —

Factory-Installed Option

Watts —

Input Watts to Motor

*Standard low-medium static drive range for the 020 size is 910 to 1095 rpm. Standard low-medium static drive range for the 024 size is 1002 to 1225 rpm. Alternate high-static drive range for the 020 size is 1069 to 1287. Alternate high-static drive range for the 024 size is 1193 to 1458 rpm. Other rpms require a field-supplied drive.

NOTES:

1.Maximum continuous bhp for the 020 size is 5.90. Maximum continuous bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (380, 460 v). The maximum continuous watts for the 020 size is 5180. The maximum continuous watts for the 024 size is 7915

(208/230, 575 v) or 8640 (380, 460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

2.Static pressure losses (i.e., EconoMi$er) must be added to external static pressure before entering Fan Performance table.

3.Interpolation is permissible. Do not extrapolate.

4.Fan performance is based on wet coils, clean filters, and casing losses. See Table 12 for accessory/FIOP static pressure information.

5.Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

6.Use of a field-supplied motor may affect wiring size. Contact your Carrier representative for details.

20

Page 20
Image 20
Carrier 50TJ016-028 specifications Fan Performance 50TJ020