VENTILATION AIR (Minimum Position Set Up) — If ven- tilation air is not required, skip this section. If ventilation air is required, perform the following:

1.The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit con- nection board.

2.Locate the minimum position (MIN POS) potentiometer. Turn the potentiometer full CCW to fully close the out- door air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 16.

3.Replace the filter access panel. See Fig. 18. Ensure the fil- ter access panel is securely engaged.

4.Calculate the minimum airflow across the EconoMi$er.

a.Calculate % of outside air using the following formula.

% Outdoor air through EconoMi$er

Personal Injury Hazard. Avoid possible injury by keep- ing fingers away from damper blades.

Step 9 — Install All Accessories — After all the factory-installed options have been adjusted, install all field- installed accessories. Refer to the accessory installation instruc- tions included with each accessory.

MOTORMASTER® I CONTROL INSTALLATION (50TJ016 and 020 Only)

Install Field-Fabricated Wind Baffles — Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 25 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

% Outdoor air =

Mixture Temp – Return Air Temp

Outdoor Temp – Return Air Temp

b. Multiply total CFM by percentage outdoor air, this gives outdoor air volume in CFM.

To avoid damage to the refrigerant coils and electrical com- ponents, use recommended screw sizes only. Use care when drilling holes.

Unoccupied Control (Part number on the control

must be AD-DME1701-1 or AD-DME1711-1.)

Outdoor Air Enthalpy

 

 

 

CROUTENT001A00

 

Unoccupied

 

 

 

Contact

470 ohm

 

 

 

5 watt

 

T

Violet

Resistor

C

 

O

 

 

O

U

 

 

M

T T

 

 

 

PW

 

 

 

 

Tan

OAT

 

Violet

 

 

COM

 

W hite

 

 

24 VAC must be present on BI for the system to be unoccupied.

OAH

 

Red

 

+15V

 

 

 

 

 

 

 

 

Tan

 

 

 

 

 

 

 

 

RAT

 

 

 

 

 

 

 

 

 

 

Violet

 

COM

 

 

 

 

 

 

 

 

 

RAH

 

 

 

 

 

 

 

 

W hite

+15V

 

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

CO 2(+)

 

 

 

 

 

 

 

 

 

 

CO 2

 

 

 

 

 

COM

 

 

 

 

 

DAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

REM

 

POT

 

 

 

 

COM

 

 

 

 

LED

 

 

 

 

 

 

 

 

COM

 

 

 

 

Violet

C TO

O U

M T T

PW

Remote

Minimum Position

1k ohm Potentiometer

20 mA LED

Remote

LED

Field-supplied W iring

Return Air Enthalpy

CRRETENT001A00

CO2 Sensors:

33ZCSENCO2

 

 

2 to 10 VDC at

 

 

0 to 2000 ppm

NOT 2 USED

VAC24 VA20

Line

 

 

 

 

Voltage

1

 

 

-

 

 

W iring Included

Fig. 24 — Typical EconoMi$er Sensor Wiring

15

Page 15
Image 15
Carrier 50TJ016-028 specifications Motormaster I Control Installation 50TJ016 and 020 Only