Fig. 32 — 50TJ016 Evaporator-Fan
Motor Section
Belt Tension Adjustment — To adjust belt tension:
1.Loosen fan motor bolts.
2.Adjust belt tension:
a.Size 016 Units: Move motor mounting plate up or down for proper belt tension (1/2 in. deflection with one finger).
b.Size
3.Tighten nuts.
4.Adjust bolts and nut on mounting plate to secure motor in fixed position.
Condenser-Fan Adjustment
50TJ016,020 UNITS (Fig. 34)
1.Shut off unit power supply.
2.Remove access panel(s) closest to the fan to be adjusted.
3.Loosen fan hub setscrews.
4.Adjust fan height on shaft using a straightedge placed across the fan orifice.
5.Tighten setscrews and replace panel(s).
6.Turn on unit power.
50TJ024,028 UNITS (Fig. 35)
1.Shut off unit power supply.
2.Remove fan
3.Adjust fan height on unit, using a straightedge placed across the fan orifice.
4.Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft.
5.Fill hub recess with permagum if rubber hubcap is missing.
NOTE: A
Fig. 33 — 50TJ020-028 Evaporator-Fan
Motor Section
NOTE: Dimensions are in inches).
Fig. 34 — Condenser-Fan Adjustment,
50TJ016,020
NOTE: Dimensions are in inches.
Fig. 35 — Condenser-Fan Adjustment,
50TJ024,028
26