Carrier Install Supply Grille, Pre-Start-Up, a50-8302.eps, 50VS Unit Airflow Arrangements

Models: 50VS

1 24
Download 24 pages 43.68 Kb
Page 17
Image 17
Step 12 — Install Supply Grille

Step 12 — Install Supply Grille

Refer to Fig. 2, 3, and 12 to determine grille size and location based on the type and size of the unit cabinet/chassis combina- tion. Perform the following to install supply grilles over the cabinet discharge openings.

1.To prevent supply air from short circuiting back into the return air panel a supply duct extension(s) is provided with each cabinet.

2.Insert the grille into the cabinet supply duct extension(s). Assure that the grille flange rests against the drywall cov- ering the cabinet.

3.Secure the grille to the drywall with the screws provided.

NO SUPPLY OPENINGS

NA

 

 

 

NC

 

NB

 

 

 

 

 

 

 

 

 

 

 

SINGLE SUPPLY

 

SC

 

SA

 

SB

 

 

 

 

 

 

 

 

 

 

 

 

a50-8302.eps

 

SG

 

 

 

SE

 

 

 

SF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRE-START-UP

Check the following before system start-up.

1.Balancing/shutoff valves: Ensure that all isolation valves are open and water control valves are wired.

2.Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/break- ers are properly sized. Verify that low voltage wiring is complete.

3.Entering water and air: Ensure that entering water and air temperatures are within operating limits of Table 9.

DOUBLE SUPPLY

DB

DC

DA

DF

DG

DE

 

 

 

DK

 

 

 

 

DL

 

 

 

 

DJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRIPLE SUPPLY

 

 

 

SL

 

 

 

SJ

 

 

 

SK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY RETURN

DRAIN

RISERS

LEFT

RIGHT

CABINET

FRONT

Supply Grille Sizes and Arrangements

UNIT

DISCHARGE (in.)

Single

Double

Triple

 

50VSA,B

14x12

10x8

10x8

(Small Cabinet)

50VSC,D

14x12

10x8

10x8

(Small Cabinet)

50VSE,F

14x12

10x8

10x8

(Small Cabinet)

50VSG,H

14x12

10x8

10x8

(Small Cabinet)

50VSI,J

16x14

12x10

12x10

(Large Cabinet)

50VSK,L

16x14

12x10

12x10

(Large Cabinet)

50VSM,N

16x14

12x10

12x10

(Large Cabinet)

 

TA

 

 

 

TE

 

 

 

 

 

 

 

TJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY AIR TO ROOM

RETURN AIR FROM ROOM

Field-supplied and installed piping Cross hoses in slave cabinet

(36 in. hoses required in slave unit)

SR a50-8302.eps R

C PRE-START-UP C

RS Supply Grille Sizes and Arrangements S

SLAVE

 

 

 

 

 

 

MASTER

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

Dimension to suit local codes

C — Condensate Drain

 

and installer

R — Return

S — Supply

NOTES:

1.Refer to the table and the airflow arrangements above to determine grille size and location based on the type and size of the unit cabinet/chassis combination.

2.The riser compartment is defined as being the rear of each unit. Supply air grilles and return air/access panel can be any side except rear.

3.Return air location also denotes the control location and servicing access.

4.Single discharge openings are not recommended for 50VSI-VSN units. Triple discharge openings are not recommended for 50VSA-VSD units.

Fig. 12 — 50VS Unit Airflow Arrangements

17

Page 17
Image 17
Carrier 50VS specifications Install Supply Grille, Pre-Start-Up, a50-8302.eps, Supply Grille Sizes and Arrangements