to determine the unit error. If a digital communicating thermo- stat is used DIP switch 3 must be set in the “Off” position. If a
DIP SWITCH 4 (RV at Cooling = Off/RV at Cooling = On) Reversing Valve Operation — DIP switch 4 is used to deter- mine the reversing valve (RV) position in the Cooling mode (deenergized/energized). This function is used only when a 24- vac thermostat is used and is determined by the reversing valve output of the thermostat in the Cooling mode. If the thermostat deenergizes the reversing valve in the Cooling mode then set the DIP switch in the “Off” position. If the thermostat ener- gizes the reversing valve in the Cooling mode set the DIP switch in the “On” position.
DIP Switch 5 (Com2 = Off/BacNet™ or LonWorks®) (Com1 = On/Communicating Thermostat)
DIP Switch 6 (Com2 modbus address) DIP Switch 7 (Com2 modbus address) DIP Switch 8 (Com2 modbus address)
Standard 24-vac Sequence of Operation
RANDOM START DELAY — When the unit is first pow- ered “On” the control microprocessor will generate a random number to determine the start delay of the compressor opera- tion (3 to 5 minutes). This delay is used to prevent multiple units from cycling “On” at the same time. The purpose is to prevent a large power load on the building electrical system af- ter a power outage. After the number, or delay time, is generat- ed the microprocessor will use this time to determine the mini- mum amount of time that must be delayed before the compres- sor is cycled “On” after a demand is received from the thermostat.
ANTI SHORT CYCLING DELAY — After the random start delay is generated the microprocessor will use this time to determine the minimum amount of time that must be delayed before the compressor is cycled “On” after a demand is received from the thermostat. This allows the refrigerant sys- tem to equalize in pressure and prevents
MINIMUM COMPRESSOR RUNTIME — The minimum compressor runtime of each cycle, heating or cooling, is 60 seconds. Once the compressor is energized it will not de- energize, even if the thermostat input is removed, until the min- imum runtime is satisfied.
COOLING FIRST STAGE (Y1, O) — When the micropro- cessor receives (Y1, O) at the
The microprocessor will then verify that the
COOLING SECOND STAGE (Y1, Y2, O) — When the mi- croprocessor receives (Y1, Y2, O) at the
HEATING FIRST STAGE (Y1) — When the microproces- sor receives (Y1) at the
The microprocessor will then verify that the anti short cy- cling delay has been satisfied. Once the anti short cycling delay has been satisfied the compressor and will cycle “On.” The blower will cycle “On” in high speed 15 seconds after the com- pressor is cycled “On.”
FAN ONLY MODE (G) — The fan only mode can be used only with a
START-UP
1.Turn on the line power to all heat pumps.
2.Turn the thermostat fan position to “ON.” Blower should start.
3.Balance airflow at registers.
4.Adjust all valves to their full open positions. Room temperature should be within the
5.Two factors determine the operating limits of the 50VS heat pumps:
a.Adjust the unit thermostat to the warmest setting. Place the thermostat mode switch in the “COOL” position. Slowly reduce thermostat setting until the compressor activates.
b.Check for cool air delivery at the unit grille within a few minutes after the unit has begun to operate. NOTE: Units have a 3 to 5 minute time delay in the control circuit that can be eliminated on the microprocessor control board. See test mode described in the DIP Switch Settings and Opera- tion section.
c.Check the elevation and cleanliness of the conden- sate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is filled to pro- vide a water seal.
d.Refer to Table 12. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, see Troubleshooting section.
e.Check air temperature drop across the air coil when compressor is operating. Air temperature drop should be between 15 and 25 F.
19