Carrier D2-3466-2 For Carrier Drives, Chapter, Identifying Parameter Defaults, Parameter No

Models: D2-3466-2

1 38
Download 38 pages 49.13 Kb
Page 15
Image 15
Identifying Parameter Defaults

CHAPTER 4

Identifying Parameter Defaults

For Carrier Drives

Use the following table to identify and set the parameter defaults for Carrier drives.

Important: Setting P.050 (Restore Defaults) to ON will restore the drive to Reliance defaults, not Carrier defaults. If this has been done, set the following parameters to restore Carrier defaults.

Parameter No.

Parameter Name

Setting

 

 

 

 

P.000

Control Source

rE

 

 

 

 

P.001

Accel Time 1

8

 

 

 

 

 

P.002

Decel Time 1

20

 

 

 

 

 

P.003

Minimum Speed

0.5

 

 

 

 

 

P.004

Maximum Speed

Job-specific (50 or 60)

 

 

 

 

P.005

Current Limit

110

 

 

 

 

 

P.0091

Terminal Strip Analog Input Offset

-10

 

P.0101

Terminal Strip Analog Input Gain

0.99 (50LR4060, 64LR4060)

 

 

1.030 (41LR4060)

P.011

Terminal Strip Analog Input Configure

4

 

 

 

 

 

P.013

Output Relay Configuration

2

 

 

 

 

 

P.027

Forward/Reverse Configuration

1

 

 

 

 

 

P.028

Speed Display Scaling

Job-specific

 

 

 

 

P.043

Fault Auto Reset Attempts

10

 

 

 

 

 

P.044

Fault Auto Reset Time

30

 

 

 

 

 

P.052

AUTO/MAN Key Disable

ON

 

 

 

 

H.000

Motor Nameplate Volts

Job-specific

H.001

Motor Nameplate Base Frequency

Job-specific

 

 

 

H.002

Motor Nameplate Amps

1.03 x Motor Nameplate Amps

 

 

 

H.021

AC Line Volts

Job-specific

 

 

 

H.022

Overfrequency Limit

Job-specific (57 or 69)

 

 

 

 

r.001

Analog Output 1 Source

4

 

r.0021

Analog Output 1 Offset

60 (50LR4060, 64LR4060)

 

 

135 (41LR4060)

r.0031

Analog Output 1 Gain

0.505 (50LR4060, 64LR4060)

 

 

0.503 (41LR4060)

r.035

Relay Output 1 (NO) Configuration

5

 

 

 

 

 

r.036

Relay Output 2 (NO/NC) Configuration

2

 

 

 

 

 

r.037

Relay Output 3 (NO/NC) Configuration

1

 

 

 

 

 

r.046

Relay Output 3 Delay Time

-999

 

 

 

 

 

r.050

Speed Detection Level 1

35

 

 

 

 

 

1These parameters must be tuned or calibrated per the VFD Control Verification procedures (running and non-running) found in the Carrier 19XR/XRV Start-Up, Operation, and Maintenance Instructions on pages 59-60.

For job-specific parameters, refer to the 19XR, XRV Start-Up, Operation, and Maintenance Instructions manual (531-982) for further instructions. For descriptions of all parameters, refer to the LiquiFlo Software Start-Up and Reference manual (D2-3410).

Identifying Parameter Defaults For Carrier Drives

4-1

Page 15
Image 15
Carrier D2-3466-2 For Carrier Drives, Chapter, Identifying Parameter Defaults, Parameter No, Parameter Name, Setting