Table 6.3 – List of Fault Codes (Continued)
| Fault |
|
|
Code | Description | Fault Cause | Corrective Action |
OCb | Overcurrent | DC voltage too high. | Check parameters H.006, H.007. |
| (at DC braking) |
|
|
OCd | Overcurrent (at | Overcurrent condition occurred while | See OC fault corrective actions. |
| deceleration) | decelerating. | Increase deceleration time (P.002, |
|
| Deceleration time too short. | P.018, P.022). |
OF | Overfrequency | Drive has exceeded maximum | Vector: Check parameters Encoder |
|
| allowable output frequency. | PPR (U.001), Motor Poles (U.002), |
|
| Regenerating energy is too high. | Base Frequency (U.003). |
|
| Stability or slip compensation circuit | V/Hz: Check DC bus voltage; increase |
|
| adds frequency reference. | decelerating time. Check values Max |
|
| If H.016 ON, searching current is too | Speed (P.004) / Overfreq. (H.022). |
|
| high. Motor is too small. | Check slip compensation (H.004). |
|
|
| If H.016 ON, check motor size versus |
|
|
| Power Module size, recheck setting of |
|
|
| P.005 (too high). |
OH | Drive | Cooling fan failure. | Check ambient temperature, cooling |
| overtemperature |
| fan, minimum clearances around drive. |
OL | Motor overload | Excess motor current. | Vector: Check actual/Motor Rated |
|
| V/Hz: Torque boost too high, therm. | Nameplate Amps (U.004) |
|
| overload level too low. | V/Hz: Check actual current/Torque |
|
|
| Boost (H.003). |
|
|
| Check that Power Module is sized |
|
|
| correctly. |
|
|
| Reduce load on motor (for example, at |
|
|
| low frequency). |
|
| Excess load on motor, for example, at | Check that Power Module is sized |
|
| too low speeds. | correctly. Reduce load on motor (e.g., |
|
|
| at low frequency). |
|
| Loss of phase connection. | Check output lines to the motor. |
OPL | Motor output phase | Phase lost between drive and motor. | Check connections and cable of all 3 |
| loss |
| phases and motor windings. Replace |
|
|
| any damaged cable. |
OSP | Overspeed | RPM above 130% Maximum Speed | Check Encoder PPR (U.001), Motor |
| (Vector only) | (P.004), speed regulator response not | Poles (U.002), Base Frequency |
|
| optimized. | (U.003), Motor Nameplate RPM |
|
|
| Speed (U.005). Check Reg. |
|
|
| Proportional (U.012) Integral Gain |
|
|
| (U.013) |
PUc | Missing Power | Bad or disconnected cable between | Check cables between Regulator |
| Module ID | Regulator and Power Module. | board and Power Module. |
| connector |
|
|
PUn | Power Module not | Drive parameters have been restored | Power Module must be configured by |
| identified | to | Reliance service personnel. |
|
| not been configured to match Power |
|
|
| Module. |
|
PUo | Drive power | Power Module overloaded. | Check load to Power Module. |
| electronic | Too high DC Braking Current | Check Power Module sizing versus |
| overload | (H.007) or Torque Boost (H.003). | application. Check DC Braking Current |
|
|
| value (H.007). Check Torque Boost |
|
|
| (H.003). |
SF |
| See parameter U.009 | |
| (Vector only) |
|
|
|
|
|
|
Carrier VFD Quick Reference |