Carrier D2-3466-2 instruction manual 6-10, Code, Description, Fault Cause, Corrective Action

Models: D2-3466-2

1 38
Download 38 pages 49.13 Kb
Page 28
Image 28

Table 6.3 – List of Fault Codes (Continued)

 

Fault

 

 

Code

Description

Fault Cause

Corrective Action

OCb

Overcurrent

DC voltage too high.

Check parameters H.006, H.007.

 

(at DC braking)

 

 

OCd

Overcurrent (at

Overcurrent condition occurred while

See OC fault corrective actions.

 

deceleration)

decelerating.

Increase deceleration time (P.002,

 

 

Deceleration time too short.

P.018, P.022).

OF

Overfrequency

Drive has exceeded maximum

Vector: Check parameters Encoder

 

 

allowable output frequency.

PPR (U.001), Motor Poles (U.002),

 

 

Regenerating energy is too high.

Base Frequency (U.003).

 

 

Stability or slip compensation circuit

V/Hz: Check DC bus voltage; increase

 

 

adds frequency reference.

decelerating time. Check values Max

 

 

If H.016 ON, searching current is too

Speed (P.004) / Overfreq. (H.022).

 

 

high. Motor is too small.

Check slip compensation (H.004).

 

 

 

If H.016 ON, check motor size versus

 

 

 

Power Module size, recheck setting of

 

 

 

P.005 (too high).

OH

Drive

Cooling fan failure.

Check ambient temperature, cooling

 

overtemperature

 

fan, minimum clearances around drive.

OL

Motor overload

Excess motor current.

Vector: Check actual/Motor Rated

 

 

V/Hz: Torque boost too high, therm.

Nameplate Amps (U.004)

 

 

overload level too low.

V/Hz: Check actual current/Torque

 

 

 

Boost (H.003).

 

 

 

Check that Power Module is sized

 

 

 

correctly.

 

 

 

Reduce load on motor (for example, at

 

 

 

low frequency).

 

 

Excess load on motor, for example, at

Check that Power Module is sized

 

 

too low speeds.

correctly. Reduce load on motor (e.g.,

 

 

 

at low frequency).

 

 

Loss of phase connection.

Check output lines to the motor.

OPL

Motor output phase

Phase lost between drive and motor.

Check connections and cable of all 3

 

loss

 

phases and motor windings. Replace

 

 

 

any damaged cable.

OSP

Overspeed

RPM above 130% Maximum Speed

Check Encoder PPR (U.001), Motor

 

(Vector only)

(P.004), speed regulator response not

Poles (U.002), Base Frequency

 

 

optimized.

(U.003), Motor Nameplate RPM

 

 

 

Speed (U.005). Check Reg.

 

 

 

Proportional (U.012) Integral Gain

 

 

 

(U.013)

PUc

Missing Power

Bad or disconnected cable between

Check cables between Regulator

 

Module ID

Regulator and Power Module.

board and Power Module.

 

connector

 

 

PUn

Power Module not

Drive parameters have been restored

Power Module must be configured by

 

identified

to power-up defaults. Regulator has

Reliance service personnel.

 

 

not been configured to match Power

 

 

 

Module.

 

PUo

Drive power

Power Module overloaded.

Check load to Power Module.

 

electronic

Too high DC Braking Current

Check Power Module sizing versus

 

overload

(H.007) or Torque Boost (H.003).

application. Check DC Braking Current

 

 

 

value (H.007). Check Torque Boost

 

 

 

(H.003).

SF

Self-tuning status

 

See parameter U.009

 

(Vector only)

 

 

 

 

 

 

6-10

Carrier VFD Quick Reference

Page 28
Image 28
Carrier D2-3466-2 instruction manual 6-10, Code, Description, Fault Cause, Corrective Action