Vertical Termination - Direct Vent ONLY

A vertical vent system must terminate no less than 8’ (2.44 m) and no more than 40’ (12 m) above the appli- ance flue collar. A 2¹⁄" restrictor plate (supplied) must be used, where specified, in all vertically terminated vent systems. (Refer to Figure 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with stove directly at stove outlet. A vertically terminated vent system must also conform to the following criteria:

No more than two 90° elbows may be used.

Two 45° elbows may be substituted for one 90˚ elbow. No more than six elbows may be used.

Vent must rise a minimum of 2 feet before offset is used.

Termination height must conform to roof clearance as specified in Figure 9.

 

40

 

 

39

 

 

38

All Vertical Termi-

 

37

nations in this area

 

36

pipe.)

Require use of

34

the 2¹⁄” Restrictor

 

35

 

vent

33

Plate*

 

 

the

32

 

31

 

of

 

 

 

top

30

 

 

 

to the

29

 

28

 

collar

27

 

feet)(in flue

25

 

 

26

 

appliance

 

Vertical terminations

 

 

Run

24

must be within this area

Vertical the

23

 

22

 

 

21

 

from

20

 

19

 

(Measure

 

18

 

 

16

Unacceptable

 

15

Venting Configuration

 

14

 

 

13

 

 

12

 

 

11

 

 

10

 

 

9

 

 

8

 

 

7

 

 

6

 

 

5

 

 

4

 

 

3

 

 

2

 

1No offset may be used

0

within this area

 

12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Horizontal Run (in feet)

ST132a

Fig. 8 Vertical vent termination window.

*The Restictor Plate is used on Direct Vent installations only.

Jefferson Direct Vent /Natural Vent Gas Heater

Vent Termination Clearances

When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 9.

Important: All vent clearances must be maintained. Check your vent termination clearances against Figures 9 and 10.

The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.

The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.

Some considerations are:

Obstructions or impediments to venting.

Nearby combustible materials that could come into contact with combustion exhaust gases.

Other nearby openings {within 9” (229 mm)} through which exhaust gas could reenter the building.

All vegetation within 3’ (914 mm) that may interfere with the draft.

Other factors that influence where the installation will be sited include the location of outside walls, where additional heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.

IMPORTANT

Direct Vent Only

The horizontal termination must not be recessed into the exterior wall or siding.

Horizontal vent runs must be level toward the vent termination.

Clearances around the vent termination must be maintained.

For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have restricted access for connecting the Hori- zontal Vent Cap straps to the vent pipe. See the maker’s instructions for recommended installa- tion procedures.

30004177

9

Page 9
Image 9