Chapter 2 Power and Cooling
Facility Cooling Requirements
Heat dissipation and external cooling requirements for the
•Heat dissipation: 27,350 BTUs per hour
•External cooling requirements: 2.3 tons
To ensure that the site provides the proper air circulation for the system:
•Make certain that the site is as dust free as possible. Dusty environments can clog the air filter or power supply intake vents, reducing the cooling airflow through the system.
•Allow sufficient airflow by maintaining a minimum of 6 inches (15.2 cm) of clearance at both the inlet and exhaust openings on the chassis and the power modules. If airflow is blocked or restricted, or if inlet air is too warm, an