1.1 Specification
"User Text Display Address, location and fault description.
"Dimensions H x W x D (mm) 270 x 332 x 90
"Maximum System Capacity 250 self contained luminaires depending on system type
"Weight (Including Battery) 6 Kg
"LED Indicators/LC Display LEDs are;
Power On, Emergency Mode, General
Fault, System Fault, Test In Progress, Disable,
Scroll and Luminaire Groups
LCD is 2 lines x 40 characters
"User Controls Soft touch five button keypad
"User Function Menu Enable/Disable Units/SCAELInterface LED Test, Test Mode,
Voltage/Current Display and Print options using RS232
Portable Printer
"Remote Signal Volt free change over Contact (1A 24V DC Relay)
"Communications Port RS232 (Printer) and RS485 (Repeater)
"Sealed Lead Acid Batteries 24V system comprising of 2 x 12V @ 3.2Ah each
"Battery Charger 800mA, constant voltage, temperature compensated
"Loop Output 26V Stabilised
"Loop Communication 9V pulses superimposed on the 26V line
"Temperature Range Battery charger compensated 0° to 40°(C
"Commissioning Site Software Download at initialisation from a PC
"Memory life(without power) 10 Years
"Working Memory 1 week for test result information
"Number of Loops 1
5