1.2 Features
"80 Character display showing the exact address and location of any fault identified.
"16 group capability with individual group indicators in addition to text display.
"One loop giving a total of 250 address capacity.
"Two self contained 12 volt rechargeable batteries for 6 hour standby with a fully loaded loop.
"Full text downloading in seconds using PC compatible computer (i.e. Laptop).
"Self learning of SCAEL Interfaces addresses to aid commissioning
"In the event of Fault, display shows location text, address, charge current and battery voltage.
"Stabilised 24V output independent of Battery voltage during Mains fail.
Fault Relay
Volt free change over contact is provided (see section 7.0), it is rated at 1A / 24V DC
The relay operates upon any Fault condition.
Loop Wiring
Electrical insulation test should not be carried out if the loop cables are connected to the
EasiCheck panel, or to the fittings or to any electronic circuitry.
Before connecting the wiring to the EasiCheck panel, the wiring should be tested for continuity,
polarity, short circuit and earth faults.
Networking
Amaximum of 64 EasiCheck Panels can be networked by fitting of additional network cards.
The Panels are inter connected in a network loop (two in, two out). Any EasiCheck Panel
reporting a fault in the system will be shown on all Panels. The Fault may be viewed and reset
from any Panel. See page 11 for cable type
6