2.0 Programming the EASICHECK™ SCAEL Interface.
Before the SCAEL Interface is connected it must be programmed in order for the
EASICHECK™ Panel to recognise it as part of the system. This is done with an
EASICHECK™ hand held programming unit. The programming unit has two spring loaded
connections which are to be held briefly on to the SCAEL Interface ‘TELE/LOOP’ connections.
See Diagram;
Programmer SCAEL INTERFACE
Switch on the programming unit by pressing the top right button marked On/Off. After a few
seconds the programming unit display will show the next address number due to be
programmed. Hold the spring terminal against the SCAEL Interface and press Program. The
programmer will show ‘Pro’ to register address acceptance and then the address number will
increment by one ready for the next interface. The interface is now ready to be fitted. Repeat
this until all of the interfaces have been programmed.
Note: If you are unsure as to which address the SCAEL Interface has been programmed for,
then with the programmer switched off, hold the spring terminals against the SCAEL Interface
and switch on the programmer. After a short delay the programmer display will flash the
number of the SCAEL Interface address and then return to the next address number to be
programmed.
The SCAEL unit contains a latching relay. During transit it is possible for the relay to change
state, even though it is not powered up. During programming the programmer will
automatically restore the relay to its correct position.
2.1 Installation of the SCAEL Interface.
The SCAEL Interface should be connected into the Luminaire by following the instructions
supplied.
Attach the address label to the Luminaire. Sets of address labels are available separately.
The interface is connected in series with the existing battery pack and the LED is fitted through
a hole in the gear tray to display healthy or fault status. The incoming mains live charge and
live switched (maintained luminaires only) should be wired into the screw terminal block and
the corresponding flying wires for each should be connected into the luminaires in the usual
manner.
The interface continually monitors the battery voltage and charge current which is interrogated
by the EASICHECK™ Control Panel and checked for correctness. Any luminaire found to be
incorrect will have it’s Green LED switched to Amber and the Control Panel will display the
Address number, location and a fault description.
7
EASICHECK™
001
PROGRAM ON / OFF
LIVE SWITCH (OUT)
RED
BROWN
LIVE SWITCH (IN)
LIVE CHARGE (IN)
BATTERY IN
BATTERY OUT
RED = +VE
BLACK = -VE
SCAEL INTERFACE
TELE/LOOP
LED
LIVE CHARGE (OUT)
UNITS
TENS