SLR • SLC • SLD OPERATOR INSTALLATION GUIDE
CHARGER BOARD SLEEP MODE
When primary AC power is not available, the operator will continue to operate in battery only mode if the charger board is set in its RUN mode (see Battery Backup Charger Configuration). Accessories wired into the operator will continue to draw power, even when the operator is not opening or closing the gate. This can dramatically reduce the amount of standby time available from the batteries.
To extend the available standby time, the charger board has a “sleep” mode feature which will turn off power to all controls except for any that are wired according to the schematics below. By removing the black jumper cap JP1 located in the upper right hand corner of the charger board this feature can be enabled. After fifteen minutes of inactivity, all controls ex- cept those wired as shown below will turn off. Those wired as shown will continue to have power at all times and will upon activation generate first a “wake” signal that will power all controls back up, and then create either an open signal or single button signal, depending on how the wire jumper shown below is connected.
JP1
OPEN JUMPERCAP WAKE
TERMINALTERMINAL
CHARGER BOARD
- 14 -