SLR • SLC • SLD OPERATOR INSTALLATION GUIDE

WIRING SPECIFICATIONS

1.Select from the chart at the bottom of this page corre- sponding to the model, voltage and horsepower rating of your operator.

2.The distance shown on the chart is measured in feet from the operator to the power source. DO NOT EXCEED THE MAXIMUM DISTANCE. These calculations have been based on standard power supplies with a 10% allowable voltage drop. If the available voltage is less than the stan- dard rating, the wire lengths listed may be longer than what your application will handle. If this is the case, you should not allow your wire length to reach the upper end of the chart for the gauge of wire you are using.

3.When large-gauge wire is used, a separate junction box (not supplied) may be needed for the operator power con- nection.

4.All control devices are now 24VDC, which can be wired considerable distances.

5.Wire length calculations are based on the National Elec- trical Code, Article 430 and have been carefully deter- mined based on motor inrush, brake solenoids, and op- erator requirements.

6.Connect power in accordance with local codes. All power wiring should be done by a licensed electrician. The green ground wire must be properly connected.

7.Wire insulation must be suitable to the application.

8.Control wiring must be run in a separate conduit from power wiring. Running them together may cause interference and faulty signals in some accessories.

9.Electrical outlets are supplied in all 115VAC models for convenience with occasional use or low power consump- tion devices only. If you choose to power dedicated equip- ment from these devices, it will decrease the distance for maximum wire length and the charts will no longer be accurate.

10.A three-wire shielded conductor cable is required to con- nect master and slave operators. You must use Belden 8760 Twisted Pair Shielded Cable (or equivalent) only – OSCO part number 2500-1982, per foot). See page 9 for details of this connection, as well as dip switch selection.

Note: The SHIELD wire should be connected in both the master and slave operators.

USE COPPER WIRE ONLY!

 

MODEL

SLR

 

 

Power Wiring

 

 

 

 

 

 

Volts

Max Distance

 

Wire

& HP

Single

Dual

 

Gauge

 

 

 

 

 

 

115V

316

 

158

 

12

 

502

 

251

 

10

 

800

 

400

 

8

1/2

1272

 

636

 

6

HP

2022

 

1011

 

4

 

 

 

 

 

Volts

Max Distance

 

Wire

& HP

Single

Dual

 

Gauge

 

 

 

 

 

 

230V

764

 

382

 

12

 

1218

 

609

 

10

 

1936

 

968

 

8

1/2

3076

 

1538

 

6

HP

4896

 

2448

 

4

 

 

 

 

 

 

MODEL SLR SLC

ACCESSORY WIRING

MODEL SLC

Power Wiring

Volts &

Max Distance

Wire

Volts &

Max Distance

Wire

Volts &

Max Distance

Wire

HP

Single

Dual

Gauge

HP

Single

Dual

Gauge

HP

Single

Dual

Gauge

115V

222

111

12

208V

760

380

12

230V

894

447

12

 

354

177

10

 

1200

600

10

 

1422

711

10

 

566

283

8

 

1924

962

8

 

2264

1132

8

1/2

900

450

6

1/2

3060

1830

6

1/2

3600

1800

6

HP

1430

715

4

HP

4864

2432

4

HP

5724

2862

4

115V

178

89

12

208V

604

302

12

230V

710

355

12

 

282

141

10

 

958

478

10

 

1128

564

10

 

450

225

8

 

1526

763

8

 

1796

898

8

3/4

716

358

6

3/4

2424

1212

6

3/4

2852

1426

6

HP

1140

570

4

HP

3856

1928

4

HP

4538

2269

4

115V

160

80

12

208V

544

272

12

230V

640

320

12

 

254

127

10

 

864

432

10

 

1016

508

10

 

406

203

8

 

1374

686

8

 

1616

808

8

 

646

323

6

 

2184

1092

6

 

2570

1285

6

1HP

1026

513

4

1HP

3476

1738

4

1HP

4090

2045

4

All Models

Volts

Maximum

Wire

Distance (ft.)

Gauge

 

 

 

 

24VAC

250

14

350*

12

 

 

 

 

24VDC

0-2000

14

 

 

 

*Over 350 ft. use DC power.

 

MODEL

SLD

 

 

Power Wiring

 

 

 

 

 

 

Volts

Max Distance

 

Wire

& HP

Single

Dual

 

Gauge

 

 

 

 

 

 

115V

430

 

215

 

12

 

684

 

342

 

10

 

1090

 

545

 

8

1/2

1732

 

866

 

6

HP

2756

 

1378

 

4

 

 

 

 

 

 

MODEL SLD

ACCESSORY WIRING

All DC Models

Volts

Maximum

Wire

Distance (ft.)

Gauge

 

 

 

 

24VDC

0-2000

14

 

 

 

*Over 350 ft. use DC power.

- 4 -