Crown Boiler CWI069, CWI172, CWI345, CWI310, CWI103, CWI276, CWI Series, CWI241, CWI379, CWI207, CWI138

Models: CWI138 CWI241 CWI310 CWI345 CWI379 CWI276 CWI103 CWI207 CWI069 CWI Series CWI172

1 56
Download 56 pages 5.49 Kb
Page 28
Image 28
Manual background

FIGURE26a: MAINBURNERFLAME-1”BURNERS

FIGURE26b:MAINBURNERFLAME-40mm

(“HIGH ALTITUDE”) BURNERS

WARNING

FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD.

15)Check the manifold pressure and adjust if necessary. To do this, use the following procedure:

a)Connect a manometer to the inlet pressure tap on the gas valve (see Figures 27 and 28).

b)Check the inlet pressure with all gas appliances on and off. The inlet pressure at the boiler must be within the following limits regardless of what combination of appliances is firing:

Inlet Press (inches w.c.)

Natural Gas

LPGas

Min.

5.0

11.0

Max.

14.0

13.0

If the inlet pressure falls outside of these limits, find and correct the cause of the problem before proceeding further.

c)Connect a manometer to the manifold (outlet) pressure tap on the gas valve (see Figures 27 and 28).

d)Read the manifold pressure. It should be set at:

 

Natural Gas

LPGas

Manifold Press. (inches w.c.)

3.5

10.0

e)If a manifold pressure adjustment is needed, make the adjustment by turning the pressure regulator (see Figures 27 and 28) screw clockwise to raise the pressure and counter clockwise to reduce the pressure. If a manifold pressure adjustment is made, recheck the line pressure to be certain that it is still within acceptable limits. Replace the cover screw on the regulator.

28

27

Page 28
Image 28
Crown Boiler CWI069, CWI172, CWI345, CWI310, CWI103, CWI276, CWI Series, CWI241, CWI379, CWI207, CWI138 installation instructions