Crown Boiler CWI Series, CWI172, CWI345, CWI310, CWI103, CWI276 V Air for Combustion and Ventilation

Models: CWI138 CWI241 CWI310 CWI345 CWI379 CWI276 CWI103 CWI207 CWI069 CWI Series CWI172

1 56
Download 56 pages 5.49 Kb
Page 5
Image 5
V Air for Combustion and Ventilation

“X” (RH CLEARANCE)

ALL SIZES LESS TANKLESS HEATER - 18“ CWI103 - CWI241 WITH TANKLESS HTR. - 18“ CWI276 - CWI379 WITH TANKLESS HTR. - 21“

CWI207 - CWI379 WITH HIGH CAPY. TANKLESS HTR. - 24“

Manual backgroundManual background “X”

FIGURE2:CWI BOILERS-CLEARANCESTOALL

TYPESOFCOMBUSTIBLECONSTRUCTIONAND

NONCOMBUSTIBLECEILINGS,WALLS,ANDDOORS.

If the right side 24” service clearance is reduced, adequate clearance must be maintained to easily read and access the controls. Alternatively, access may be provided using a door. The right side clearances shown for boilers equipped with tankless heaters allow for removal of the tankless heater.

2)This boiler may be installed directly over a non-carpeted combustible floor.

3)The boiler must be installed on a hard level surface.

4)Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.

5)The boiler should be located as close to the chimney as possible.

6)Do not install this boiler directly on a surface that may get wet. Raise the boiler on a pad.

V Air for Combustion and Ventilation

Sufficient fresh air must be supplied for combustion, ventilation and flue gas dilution. Provisions for combustion, ventilation and flue gas dilution air for gas utilization equipment vented by natural draft must be made in accordance with local building codes or, in absence of such codes, in accordance with sections 5.3.3 and 5.3.4 (“Air for Combustion and Ventilation”) of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.

To ensure an adequate supply of combustion, ventilation and flue gas dilution air supply, start by determining whether the boiler is to be installed in a building of unusually tight construction. A good definition of a building of unusually tight construction is one which has all of the following features:

Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed

Weather stripping has been added on openable windows and doors

5

4

Page 5
Image 5
Crown Boiler CWI Series, CWI172, CWI345, CWI310, CWI103, CWI276, CWI069, CWI241, CWI379 V Air for Combustion and Ventilation