VII Gas Piping

VII Gas Piping

Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate input at a line pressure between the minimum and maximum values shown on the rating plate. For more information on gas line sizing, consult the utility or Chapter 2 of the National Fuel Gas Code.

Figure 10 shows typical gas piping connection to the CWI boiler. A sediment trap must be installed upstream of all gas controls. Install a manual shut-off valve outside the jacket and ground joint union as shown.

The boiler and its gas connection must be leak tested before placing the boiler in operation. When doing this, the boiler and its individual shut-off must be disconnected from the rest of the system during any pressure testing of that system at pressures in excess of 1/2 psi. When pressure testing the gas system at pressures of 1/2 psi or less, isolate the boiler from the gas supply system by closing its individual manual shut-off valve.

FIGURE10: GASCONNECTIONTOBOILER

*

*State of Massachusetts Requires Manual Shut-off Valve to be “T” Handle Type

12

11

Page 12
Image 12
Crown Boiler CWI345, CWI172, CWI310, CWI103, CWI276, CWI Series, CWI069, CWI241, CWI379, CWI207, CWI138 VII Gas Piping