Planning the Installation
WARNING
IMPORTANT: Observe all governing codes and ordinances during planning and installation. Contact your local building department for further information.
Electrical Requirements - U.S.A.
IMPORTANT: The information below does not apply to units equipped for use in Canada.
It is the owner’s responsibility to ensure that the electrical connection of this appliance is performed by a licensed electrician. The electrical installation, including minimum supply wire size and grounding, must be in accordance with the National Electric code ANSI/NFPA
National Fire Protection Association 1 Batterymarch Park
Quincy, Massachusetts
•The correct voltage, frequency and amperage must be supplied to the appliance from a separate, grounded, circuit that is protected by a properly sized circuit breaker or time delay fuse. Refer to the data on the range rating label.
NOMINAL ELECTRIC CIRCUIT REQUIREMENTS - U.S.A.
Range | Circuit Required | Total Connected | |
Model | Load | ||
| |||
ER36D | 240 Vac*, 60 Hz, 30 Amp. (Min.) | 6.5 kW (28 Amp.) | |
40 Amp. (Recommended) | |||
|
| ||
ER48D | 240 Vac*, 60 Hz, 50 Amp. | 10.0 kW (42 Amp.) | |
|
|
|
*
The ratings above are for reference only. Refer to the range data label for exact specifications (see page 3 for location).
•Consult local building codes for the type and minimum wire gauge to use for the power requirements on the rating label.
•Suggested wiring color code: Black, white, red and green.
•The wiring needs to be long enough to allow the range to be pulled out from the wall for service while remaining connected. See page 10 for further details.
•The wiring to the range must:
◊Have a minimum rating of 250 Volts @ 30 Amps for model ER36D, 250 Volts @ 50 amps for model ER48D.
◊Include a strain relief
◊Be terminated by tinned leads, closed loop terminals or open ended spade lugs with upturned ends
•Where local code permits, a three (3) or four (4) wire appliance cord may be used. The appliance cord must:
◊Be UL listed type SRD or SRDT
NEMA◊Be equipped with a NEMA
•Prior to range installation, have a licensed electrician install a conduit junction box or electrical receptacle according to the type of wiring used.
Electrical Requirements - Canada
It is the owner’s responsibility to ensure that the required 4 wire electrical outlet is installed by a licensed electrician as specified below prior to range installation. The electrical outlet installation, including minimum supply wire size and grounding, must be in accordance with all governing codes and ordinances.
•The correct voltage, frequency and amperage must be supplied to the appliance from a separate, grounded, circuit that is protected by a properly sized circuit breaker or time delay fuse. Refer to the data on the range rating label.
NOMINAL ELECTRIC CIRCUIT REQUIREMENTS - CANADA
Range | Circuit Required | Total Connected | |
Model | Load | ||
| |||
|
|
| |
ER36D | 240 Vac*, 60 Hz, 30 Amp. (Min.) | 6.5 kW (28 Amp.) | |
40 Amp. (Recommended) | |||
|
| ||
ER48D | 240 Vac*, 60 Hz, 50 Amp. | 10.0 kW (42 Amp.) | |
|
|
|
*
The ratings above are for reference only. Refer to the range data label for exact specifications (see page 3 for location).
•Ranges equipped for use in Canada come
4 Wire appliance cord and NEMA
•Do not modify the factory wiring. The plug is designed to insert directly into a NEMA
a licensed electrician according NEMA
Gas Supply Requirements
•Check your local building codes for the proper method of installation. In the absence of local codes, this appliance should be installed in accordance with the National Fuel Gas Code ANSI Z223.1.
•Be certain that the appliance being installed is correct for the gas service provided (natural gas or LP gas). Also, if operating the range at an altitude above 4000 feet. (1219 m) make sure it is equipped for high altitude operation. Refer to the range data plate and the table on page 3 to determine the correct model.
•See the table below for gas supply pressure requirements.
•The regulator inlet accommodates a 3/4” gas line. The range ships with a 1/2” to 3/4” adapter connected to the regulator.
GAS SUPPLY PRESSURE REQUIREMENTS*
Gas Type | Minimum | Minimum Gas | |
Manifold Pressure | Supply Pressure** | ||
| |||
Natural Gas | 5” Water Column | 6” Water Column | |
Liquid Propane (LP) | 10” Water Column | 11” Water Column |
*The gas supply pressure for testing the regulator setting shall be at least 1 inch water column (249Pa) above the specified manifold pressure
**Maximum gas supply pressure for all models: 1/2 p.s.i.
The ratings above are for reference only. Refer to the range data label for exact specifications (see page 3 for location).