Gas Supply

!WARNING

Improperly connected gas lines may result in fire, explosion, poisonous fumes, toxic gases, asphyxiation or death. Connect gas lines in accordance to national, state, provincial and local codes.

The gas supply to the infra-red heater must be connected and tested in accordance with national, state, provincial and local codes along with the guidelines in the Dayton® High Intensity Heater manual. In the United States refer to the latest edition of the ANSI Z223.1 (NFPA 54) Standard, and in Canada refer to the latest edition of the CAN/CGA B149.2 Standard.

Chart 2.3 Manifold Pressure

Important! Before connecting the gas supply to the infra-red heater(s):

Check that the gas piping and service has the capacity to handle the load of all heaters being installed, as well as any other gas appliances being connected to the supply line.

Check that the main gas supply line is of proper diameter to supply the required fuel pressures.

If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply lines in accordance with local codes.

Test and confirm that inlet pressures are correct. Refer to the rating plate for required minimum and maximum pressures (see Chart 2.3). The gas supply pipe must be of sufficient size to provide the required capacity and inlet pressure to the heater (if necessary, consult the local gas company).

E

N G L I S H

Type of

Required Manifold

Minimum Inlet

Maximum Inlet

Gas

Pressure

Pressure

Pressure

 

 

 

 

Natural

6.0 in. W.C.P.

7.0 in. W.C.P.

14.0 in. W.C.P.

 

 

 

 

Liquefied Petroleum

10.0 in. W.C.P.

11.0 in. W.C.P.

14.0 in. W.C.P.

 

 

 

 

Note: Check manifold pressure at the tap located either at the outlet of the gas valve or on the gas manifold pipe. Readings will be above atmospheric pressure during operation.

Pressure Equivalents: 1 in. W.C.P. equals .058 oz/sq. in. equals 2.49 Mbar.

To connect the gas:

!WARNING

Failure to install, operate or service this appliance in the approved manner may result in property damage, injury or death.

This heater must be installed and serviced by trained gas installation and service personnel only.

The gas outlet must be in the same room as the appliance and accessible. It may not be concealed within or run through any wall, floor or partition.

®

15

Page 15
Image 15
Dayton 3VH37, 3VH34, 5VD57, 3E462 Gas Supply, To connect the gas, Chart 2.3 Manifold Pressure, Natural, Liquefied Petroleum

3E460, 3E462, 3.00E+132, 3.00E+134, 5VD57 specifications

Dayton 3.00E+134, 5VD57, 3E462, 3E460, 3.00E+132 is a distinctive model within the Dayton series known for its advanced performance in various applications. This line of products is designed to meet the demands of both commercial and industrial sectors, showcasing a blend of efficiency, durability, and innovative technology.

One of the main features of the Dayton 3.00E+134 series is its powerful motor capabilities. The models utilize high-efficiency motors that ensure optimal energy consumption while providing robust operational performance. This not only helps to reduce utility costs but also plays a crucial role in minimizing the environmental footprint.

The technology behind Dayton products often incorporates advanced electronic controls that allow for precise adjustments and operations. This feature is particularly beneficial in environments where maintaining specific conditions is essential, such as HVAC systems and industrial processes. The electronic controls provide users with greater flexibility and range in performance settings, accommodating various operational requirements.

In terms of construction, the Dayton 3.00E+134 models are built with high-quality materials that ensure long-lasting durability. This is critical in settings where equipment is subjected to heavy usage or challenging environmental conditions. The robust design and protective coatings prevent corrosion and wear, ensuring that the equipment maintains its functionality over extended periods.

Another characteristic worth noting is the versatile range of applications for these models. They can be used in air movement, ventilation, heating, and cooling systems, making them highly valued in multiple sectors, such as manufacturing, healthcare, and commercial buildings. Their adaptability means they can seamlessly integrate into existing systems without requiring extensive modifications.

The ease of installation and maintenance is also a highlight of the Dayton 3.00E+134 series. The design facilitates quick assembly and access for servicing, saving valuable time and labor costs. Users appreciate the convenience offered, allowing them to focus on core business operations without prolonged downtime.

Furthermore, these models comply with industry standards and regulations, ensuring safety and reliability in operation. Overall, the Dayton 3.00E+134, 5VD57, 3E462, 3E460, 3.00E+132 series represents a pinnacle in engineering excellence, delivering exceptional performance across various applications while prioritizing energy efficiency and user-friendly functionality.