Delta Tau 4Ax-602804-xHxx manual E40 Macro Input Fiber/Wired Selector, JP4 Reserved for Future Use

Models: 4Ax-602804-xHxx

1 35
Download 35 pages 53 Kb
Page 17
Image 17

MACRO-CPU Hardware Reference

E5: MACRO Received Signal Detect/Bypass Mode (rev -105 and 106 only). Does not exist on rev 107 and later models.

Rev -105

Rev -104

Jumper

Description

Default

and Later

and Earlier

Type

 

 

Location

Location

 

 

 

 

 

 

Jump pins 1 and 2 to access the receiver’s signal detect operation.

Pin 1-2

 

 

 

Jump pins 2 and 3 to bypass the receiver’s signal detect

 

B-3

 

3-PIN

operation.

 

 

 

 

This jumper does not exist on MACRO-CPU versions -104

 

 

 

 

and earlier.

 

 

 

 

 

 

 

 

 

 

 

E40: MACRO Input (Fiber/Wired) Selector

Rev -105

Rev -104

Jumper

Description

Default

and Later

and Earlier

Type

 

 

Location

Location

 

 

 

 

 

 

Remove jumper to select MACRO wired (RJ45) input from J14.

Jumpered

 

 

 

Jump pins 1 and 2 to select MACRO fiber optic input from U73.

(Option A)

B-3

C-3

2-PIN

Not

 

 

 

 

 

jumpered

 

 

 

 

(Option C)

 

 

 

 

 

 

 

 

 

 

JP3: MACRO Loop back Test Select For Copper Only (rev -104 and earlier)

Rev -105

Rev -104

Jumper

Description

Default

and Later

and Earlier

Type

 

 

Location

Location

 

 

 

 

 

 

Remove jumper to select loop back in the copper interface of

jumpered

 

 

 

MACRO communications (for test purposes only).

 

 

B-1

2-PIN

Jump pins 1 and 2 for normal copper MACRO communications.

 

 

 

 

This jumper does not exist on MACRO-CPU versions -105

 

 

 

 

and greater.

 

 

 

 

 

 

 

 

 

 

 

JP4: Reserved for Future Use

3U MACRO-CPU Jumper and Switch Configurations

13

Page 17
Image 17
Delta Tau 4Ax-602804-xHxx manual E40 Macro Input Fiber/Wired Selector, JP4 Reserved for Future Use